2019-03-04 14:50:25 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| 4TH ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS |
| BELOW. BE ADVISED THAT A FOUR TIMES FEE FOR PLAN REVIEW |
| HAS BEEN ADDED TO PERMIT. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES, NOTED FOR |
| THIRD REVIEW. ANY NEW COMMENTS WILL BE LISTED AFTER |
| PREVIOUS COMMENTS. |
| |
| 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY |
| NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC |
| 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3 |
| PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG). |
| INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3 |
| PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD |
| BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS |
| AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.)(3RD |
| REVIEW: PANEL SCHEDULES ARE STILL SHOWING THE WRONG |
| VOLTAGE. PANEL A IS SHOWN BEING FED FROM B PHASE OF |
| PANEL B, WHICH WOULD CREATE A HIGH LEG ON PANEL A AND |
| PANEL A1, WHICH SHOW LOADS THAT SHOULD NOT BE CONNECTED |
| TO A HIGH LEG.)(4TH REVIEW: AS EXPLAINED IN PREVIOUS |
| REVIEWS, AND IN MEETING WITH ENGINEER, THE VOLTAGES |
| SPECIFIED IN PANEL SCHEDULES AND USED IN CALCULATION |
| SHOULD BE AS NOTED ABOVE,WHICH IS PER NEC 220.5. THIS |
| IS IMPORTANT BECAUSE THE CALCULATED CURRENT DRAW WILL |
| CHANGE BASED ON USING THE CORRECT NUMBERS. AS THIS IS A |
| HIGH LEG SYSTEM, IT SHOULD BE IDENTIFIED AS 120/240 |
| VOLT 3 PHASE AND 120/240 VOLT 1 PHASE, RESPECTIVELY. |
| ADDITIONALLY, THE HIGH LEG IS STILL SHOWN AS FEEDING |
| PANEL A. THE PANEL SCHEDULE FOR PANEL A1 HAS BEEN |
| REMOVED FROM PLAN.) |
| 2. CORRECTED. |
| 3. CORRECTED. |
| 4. CORRECTED. |
| 5. CORRECTED. |
| 6. CORRECTED. |
| 7. CORRECTED. |
| 8. CORRECTED. |
| 9. CORRECTED. |
| 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)(3RD |
| REVIEW: LOAD CALCULATION NOT CORRECT. AS EXPLAINED IN |
| MEETING WITH EOR, A 50% DEMAND FACTOR FOR RECEPTACLE |
| LOAD OVER 10,000 VA IS NOT PERMITTED AS SHOWN. ANY |
| EQUIPMENT FED FROM AN OUTLET MUST BE CALCULATED AT 100% |
| FOR NON-CONTINUOUS LOAD AND 125% FOR A CONTINUOUS LOAD. |
| NEC 215.2, 220.14(A). ADDITIONALLY, THERE ARE LOADS |
| SHOWN IN LOAD CALCULATION THAT ARE NOT SHOWN ANYWHERE |
| ELSE ON PLAN. PROVIDE CORRECTIONS.)(4TH REVIEW: LOAD |
| CALCULATION FOR SERVICE IS NOW CORRECT, BUT THE LOAD |
| CALCULATION FOR PANEL A SHOWS THE DEMAND FACTORS FOR |
| OUTLETS AT 50% FOR ANY LOAD OVER 10,000. AS STATED |
| BEFORE, THIS DEMAND FACTOR CANNOT BE APPLIED TO |
| EQUIPMENT, ONLY TO GENERAL RECEPTACLE LOADS. PROVIDE |
| CORRECTION.) |
| 11. CORRECTED. |
| 12. CORRECTED. |
| 13. CORRECTED. |
| 14. PER COMMENT REFERENCING CORDS, INSPECTOR WILL NEED |
| TO CONFIRM AT TIME OF INSPECTION THAT THE EQUIPMENT IS |
| LISTED FOR THIS TYPE OF CONNECTION PER NEC 400.7(8). |
| PROVISO WILL BE LISTED ON PLAN WHEN APPROVED. |
| 15. CORRECTED. |
| 16. CORRECTED. |
| 17. CORRECTED. |
| 18. CORRECTED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |