Plan Review Notes For Permit 18031402 |
Permit Number |
18031402 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-01-28 11:14:44 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | JOSEAN A. DUPREY | | BUILDING PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6716 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. A DOOR PRODUCT SUBMITTAL WAS PROVIDED. HOWEVER THIS | | IS BASE ON THE 2014 FBC. PLEASE PROVIDE A NEW PRODUCT | | APPROVAL PER CURRENT BUILDING CODE, ALSO PROVIDE THE | | FRONT PAGE OF THE PRODUCT APPROVAL, WE WANT TO KNOW IF | | IS IMPACT RESISTANT AND WICH PRODUCT SPECIFIC IS | | SELECTED. FBC 107 | | | | 2. PROVIDE STRUCTURAL DETAILA FOR THE NEW SIDEWALK TO | | THE ENTRANCE. FBC 107 | | | | 3. THE NEW DOOR OPENING STRUCTURAL DETAIL DO NOT | | SPECIFY HOW THE ANGLE WILL BE INSTALLED (E.I. CLIPS, IN | | THE WALL?, AT THE BOTTOL OF THE HEADER?) ALSO NO REBAR | | WAS SPECIFIED FOR THIS DETAIL. FBC 107 |
|