2019-01-28 11:14:44BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. A DOOR PRODUCT SUBMITTAL WAS PROVIDED. HOWEVER THIS
 IS BASE ON THE 2014 FBC. PLEASE PROVIDE A NEW PRODUCT
 APPROVAL PER CURRENT BUILDING CODE, ALSO PROVIDE THE
 FRONT PAGE OF THE PRODUCT APPROVAL, WE WANT TO KNOW IF
 IS IMPACT RESISTANT AND WICH PRODUCT SPECIFIC IS
 SELECTED. FBC 107
  
 2. PROVIDE STRUCTURAL DETAILA FOR THE NEW SIDEWALK TO
 THE ENTRANCE. FBC 107
  
 3. THE NEW DOOR OPENING STRUCTURAL DETAIL DO NOT
 SPECIFY HOW THE ANGLE WILL BE INSTALLED (E.I. CLIPS, IN
 THE WALL?, AT THE BOTTOL OF THE HEADER?) ALSO NO REBAR
 WAS SPECIFIED FOR THIS DETAIL. FBC 107