2019-02-06 16:46:09 | FAILED |
| |
| PROVIDE WRITTEN RESPONSE TO COMMENTS. |
| |
| 1) PROVIDE TWO COPIES OF THE SURVEY. |
| |
| 2) REPEAT COMMENT: PROVIDE A SURVEY BASED SITE PLAN |
| WHICH SHOWS WHERE THE REQUIRED ON-SITE LOADING SPACE IS |
| LOCATED. THE ALLEY MAY NOT BE USED AS THE LOADING SPACE |
| AS THERE IS NO ACCESS FROM THE ALLEY TO THE BUILDING. |
| |
| 3) THE RESUBMITTED PLANS SHOW A WALK IN COOLER |
| CONDENSING UNIT AND GARBAGE RECEPTACLES ON THE EXTERIOR |
| OF THE BUILDING. |
| |
| A. THE DIMENSIONS (LXIX) OF THE CONDENSING UNIT MUST BE |
| SHOWN ON THE SITE PLAN, AS WELL AS THE DIMENSION OF THE |
| UNIT FROM THE BUILDING. |
| B. THE SETBACK FROM THE CONDENSING UNIT TO THE WEST AND |
| NORTH PROPERTY LINES MUST BE SHOWN ON THE SITE PLAN. |
| C. THE NORTH MIXED USE DISTRICT REQUIRES THAT THE |
| CONDENSING UNIT AND GARBAGE RECEPTACLES NOT BE VISIBLE |
| FROM THE PUBLIC SIDEWALK. THE SITE PLAN NEEDS TO SHOW |
| THE SPECIFIC UNIT AND PROVIDE VERIFICATION OF THE |
| SCREENING FOR FULL HEIGHT OF THE UNIT . |
| D. THE GARBAGE RECEPTACLES NEED TO BE IN AN ENCLOSURE, |
| WHICH REQUIRES A SEPARATE PERMIT, WITH PLANS. |
| |
| 4) PROVIDE A TABLE THAT BREAKS DOWN THE SQUARE FOOTAGE |
| IN THE BUILDING TO VERIFY THAT THE PROPOSED FLOOR PLAN |
| INCLUDES AT LEAST 65 PERCENT AND NO MORE THAN 75 |
| PERCENT OF THE SQUARE FOOTAGE OF THE FACILITY DEDICATED |
| TO THE BREWERY FUNCTION. |
| |
| 5) PLEASE BE AWARE THAT THE BUSINESS MUST HOLD ONE OF |
| THE FOLLOWING LICENSES ISSUED BY THE FLORIDA DEPARTMENT |
| OF BUSINESS AND PROFESSIONAL REGULATIONS, DIVISION OF |
| ALCOHOLIC BEVERAGES AND TOBACCO: CMB, AMW, BMWC, DD. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |