Plan Review Notes
Plan Review Notes For Permit 18031402
Permit Number 18031402
Review Stop M
Sequence Number 2
Notes
Date Text
2018-10-23 11:12:212ND REVIEW FBC-2017
 PERMIT #18031402
 10/22/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A2 & M1.0: AS PREVIOUSLY REQUESTED IN THE 1ST
 REVIEW, PLEASE SEE SECTION 1009 FBC EX, AND PROVIDE
 MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES PER TABLE 403.3.1 FBC M. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR. PLEASE NOTE THAT THE BAR AND TAP ROOM AREAS ARE
 CALCULATED AT 100 PERSONS PER 1000 SF., AT 7.5 CFMS PER
 PERSON + 0.18 CFMS PER SF.
  
 2) M1.0: AN AUTOMATIC SHUTOFF DAMPER FOR THE NEW
 OUTDOOR AIR DUCT IS REQUIRED PER SECTION C403.2.4.3 FBC
 EC. INDICATE WHAT TYPE OF DAMPER WILL BE INSTALLED-
 GRAVITY OR MOTORIZED.
  
 3) M1.0: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S SPECIFICATIONS INDICATES THE
 SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR.
  
 4) A2 & M1.0: THE A2 BREWERY ROOM PLAN SHOWS ADDTIONAL
 TANKS THAT THE MEP PLANS DON'T SHOW. AS PREVIOUSLY
 REQUESTED PLEASE PROVIDE AN EQUIPMENT SCHEDULE THAT
 LISTS ALL THE BREWERY TANKS AND EQUIPMENT, AND IF A
 REMOTE CHILLER, BOILER, AND PROCESS PIPING SYSTEMS WILL
 BE INSTALLED.
  
 5) M-1 CLARIFY HOW EF-1 WAS SIZED- PROVIDE A
 CALCULATION, AND AN EQUIPMENT SCHEDULE FOR THE FAN.
  
 6) M-1: PROVIDE A FLORIDA PRODUCT APPROVAL AND/OR A
 MIAMI-DADE NOA FOR THE NEW LOUVERS.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL BREWERY
 EQUIPMENT AND TANKS WITH SHOP DRAWING APPROVAL STAMPOS
 BY THE EOR- SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS. PLEASE NOTE THAT
 ADDITIONAL COMMENTS MAY OCCUR WHEN CORRECTED PLANS ARE
 SUBMITTED FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  