Plan Review Notes
Plan Review Notes For Permit 18031402
Permit Number 18031402
Review Stop E
Sequence Number 2
Notes
Date Text
2018-10-10 12:27:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC
 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3
 PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG).
 INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3
 PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD
 BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS
 AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.)
 2. CORRECTED FOR NEW RISER DIAGRAM.
 3. PROVIDE MORE DETAIL FOR RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 (THE PLAN SHOWS AN EXISTING
 RISER DIAGRAM WITH PANEL A AND PANEL A1, AND THEN SHOWS
 A SEPARATE RISER FOR PANEL B WHICH DOES NOT INCLUDE
 PANEL A AND PANEL A1 BE ADVISED THAT ONLY ONE SERVICE
 IS PERMITTED PER NEC 230.2 AND THE RISER DIAGRAM SHOULD
 REFLECT THIS TYPE OF INSTALLATION.)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 (NOT PROVIDED.)
 7. SHOW ON PLAN ALL LIGHTING AND POWER BRANCH CIRCUITS
 EXISTING AND THOSE TO BE INSTALLED. FBC 107.2.1 (NO
 LIGHTING CIRCUITS OR FIXTURES SHOWN.)
 8. CORRECTED.
 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (NOT
 PROVIDED - NO LIGHTING SHOWN.)
 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)
 11. CORRECTED.
 12. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1 (NOT PROVIDED.)
  
 NEW COMMENTS:
  
 13. LOCATION OF PANEL B SHOWN ON PLAN DOES NOT HAVE
 PROPER CLEARANCE REQUIRED. PROVIDE CORRECTION. NEC
 110.26
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER