2018-10-10 12:27:00 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY |
| NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC |
| 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3 |
| PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG). |
| INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3 |
| PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD |
| BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS |
| AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.) |
| 2. CORRECTED FOR NEW RISER DIAGRAM. |
| 3. PROVIDE MORE DETAIL FOR RISER DIAGRAM, SHOWING ALL |
| DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD |
| SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30 (THE PLAN SHOWS AN EXISTING |
| RISER DIAGRAM WITH PANEL A AND PANEL A1, AND THEN SHOWS |
| A SEPARATE RISER FOR PANEL B WHICH DOES NOT INCLUDE |
| PANEL A AND PANEL A1 BE ADVISED THAT ONLY ONE SERVICE |
| IS PERMITTED PER NEC 230.2 AND THE RISER DIAGRAM SHOULD |
| REFLECT THIS TYPE OF INSTALLATION.) |
| 4. CORRECTED. |
| 5. CORRECTED. |
| 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| (NOT PROVIDED.) |
| 7. SHOW ON PLAN ALL LIGHTING AND POWER BRANCH CIRCUITS |
| EXISTING AND THOSE TO BE INSTALLED. FBC 107.2.1 (NO |
| LIGHTING CIRCUITS OR FIXTURES SHOWN.) |
| 8. CORRECTED. |
| 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (NOT |
| PROVIDED - NO LIGHTING SHOWN.) |
| 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.) |
| 11. CORRECTED. |
| 12. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| PRESENT. WPB FBC 105.1, 107.2.1 (NOT PROVIDED.) |
| |
| NEW COMMENTS: |
| |
| 13. LOCATION OF PANEL B SHOWN ON PLAN DOES NOT HAVE |
| PROPER CLEARANCE REQUIRED. PROVIDE CORRECTION. NEC |
| 110.26 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |