2018-11-07 12:17:50 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18031402 |
| ADD: 519 NORTHWOOD AVE. SUITE 525 |
| CONT: CALIBER CONTRACTOR |
| TEL: 561-222-1906 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: WED. NOV. 07/2018 |
| ACTION: DENIED |
| NOTICE!!!! WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. DO NOT TAKE THE OLD SHEETS AWAY, WE USE |
| THEM TO REFER TO THE CHANGES MADE. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| |
| |
| 1) THE COVERSHEET A1: COMPLIED. BUSINESS OCCUPANCY |
| DECLARED, NO OCCUPANCY SEPARATION REQUIRED BETWEEN |
| BUSINESS AND F1 OCCUPANCY. Q THE COVERSHEET A1 UNDER |
| THE HEADING PROJECT DESCRIPTION LIST THIS AS A LEVEL LL |
| ALTERATION. PLEASE NOTE THE LAST KNOWN USE (BUSINESS |
| TAX) WAS SMYRNA MARKET OR A RETAIL OCCUPANCY. THIS |
| WOULD MAKE THE USE A CHANGE OF OCCUPANCY AND UNDER THE |
| 2017 FBC-EXISTING BUILDING CODE CHAPTER 10 CHANGE OF |
| OCCUPANCY. SEE SECTION 1001.2.2.1 OF THE EXISTING |
| BUILDING CODE. PARTIAL CHANGE OF OCCUPANCY. WHERE THE |
| OCCUPANCY CLASSIFICATION OR GROUP OF A PORTION OF AN |
| EXISTING BUILDING IS CHANGED, SECTION 1012 SHALL APPLY. |
| 2A) 2ND REQUEST. SHEET A-2 SHOWS A NEW DOOR OPENING TO |
| THE EXTERIOR, A NEW 6068 DOUBLE DOORS. PLEASE PROVIDE A |
| SITE PLAN FOR WHERE THE 6068 DOORS ARE LEADING TOO. IF |
| THERE IS TO BE SEASONAL SEATING PLEASE PROVIDE ON THE |
| SITE PLAN THE ADDITIONAL SEATING. 2017 FBC-B 302.1. A |
| ROOM OR SPACE THAT IS INTENDED TO BE OCCUPIED AT |
| DIFFERENT TIMES FOR DIFFERENT PURPOSES SHALL COMPLY |
| WITH ALL OF THE REQUIREMENTS THAT ARE APPLICABLE TO |
| EACH OF THE PURPOSES FOR WHICH THE ROOM OR SPACE WILL |
| BE OCCUPIED. |
| 2B) NEW COMMENT. SHEET A2 HAS A NEW MASONRY OPENING |
| (WINDOW), PLEASE CORRECT FOR A NEW DOORWAY. 107.2.1.3 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 3) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH SECTION |
| 202.4.1. OF THE 2017 FBC-ACCESSIBILITY CODE SECTION |
| 202.4.1 DISPROPORTIONATE COST. PROVIDE AN ITEMIZED LIST |
| WHERE 0.20 % OF THE PERMIT VALUE IS GOING TO ACCESSIBLE |
| UPGRADES OR UP TO $5,000.00 IN VALUE MEETING THE EVENT |
| OF DISPROPORTIONALITY UNDER 202.4.2. |
| FBC-ACCESSIBILITY CODE SECTION 202.4.1 DISPROPORTIONATE |
| COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| 3A)2ND REQUEST. SHEETS A3 & A4 MISSING FROM THIS |
| REVIEW. SHEET A3 & A4 IDENTIFY THE FRONT DOOR AS DOOR |
| 101. PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE |
| FRONT ENTRY. GOOGLE EARTH STREET VIEW SHOWS A COLUMN AT |
| THE FRONT ENTRY AS WELL AS A HORIZONTAL BAR |
| APPROXIMATELY 36 INCHES ABOVE GRADE. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2017 FBC-EXISTING BUILDING CODE 1012.8 ACCESSIBILITY. |
| EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR |
| OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE |
| PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| |
| ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. MINIMUM |
| MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY |
| WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE |
| FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE |
| OR HINGE SIDE CLEARANCE. THE FRONT DOOR APPEARS TO HAVE |
| LESS THAN THE REQUIRED 18 INCHES FOR MANEUVERING |
| CLEARANCES. |
| |
| 3B) 2ND REQUEST. THERE IS ALSO A RAMP; PLEASE PROVIDE |
| THE SLOPE IN INCHES RISE PER FEET IN LENGTH. 2017 |
| ACCESSIBILITY CODE. 405.2 SLOPE. RAMP RUNS SHALL HAVE A |
| RUNNING SLOPE NOT STEEPER THAN 1:12. EXCEPTION: IN |
| EXISTING SITES, BUILDINGS, AND FACILITIES, RAMPS SHALL |
| BE PERMITTED TO HAVE RUNNING SLOPES STEEPER THAN 1:12 |
| COMPLYING WITH TABLE 405.2 WHERE SUCH SLOPES ARE |
| NECESSARY DUE TO SPACE LIMITATIONS. |
| |
| 3C) 2ND REQUEST. THE EXISTING RESTROOM DOES NOT ALSO |
| MEET THE REQUIREMENTS FOR A SINGLE USER TOILET ROOM |
| UNDER 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE |
| TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL |
| COMPLY WITH 603. EXCEPTIONS: |
| 1.IN ALTERATIONS WHERE IT IS TECHNICALLY INFEASIBLE TO |
| COMPLY WITH 603, ALTERING EXISTING TOILET ROOMS SHALL |
| NOT BE REQUIRED WHERE A SINGLE UNISEX TOILET ROOM |
| COMPLYING WITH 213.2.1 IS PROVIDED AND LOCATED IN THE |
| SAME AREA AND ON THE SAME FLOOR AS EXISTING IN |
| ACCESSIBLE TOILET OR BATHING ROOMS. |
| |
| 4)2ND REQUEST. MISSING SHEETS A3 & A4. SHEET A3 & A4. |
| NEW WORK NOT COVERED UNDER THE 20% DISPROPORTIONATE |
| COST. PLEASE SHOW COMPLIANCE WITH: |
| |
| 4A) 2ND REQUEST. MISSING SHEETS A3 & A4. 226.1 WHERE |
| DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF |
| FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES |
| AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| WITH 902. |
| |
| 4B) 2ND REQUEST. MISSING SHEETS A3 & A4. 226.2 |
| DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED |
| TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE |
| SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK |
| SURFACES. |
| |
| 4C) 2ND REQUEST. MISSING SHEETS A3 & A4. 206.2.5 |
| 206.2.5 RESTAURANTS AND CAFETERIAS. IN RESTAURANTS AND |
| CAFETERIAS, AN ACCESSIBLE ROUTE SHALL BE PROVIDED TO |
| ALL DINING AREAS, INCLUDING RAISED OR SUNKEN DINING |
| AREAS, AND OUTDOOR DINING AREAS (SEASONAL SEATING). |
| |
| 4D) 2ND REQUEST. 902.1 .DINING SURFACES SHALL COMPLY |
| WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING |
| SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, |
| LUNCH COUNTERS, AND BOOTHS. |
| |
| 4D)(1) 2ND REQUEST. MISSING SHEETS A3 & A4. 902.2 CLEAR |
| FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING |
| WITH 305 POSITIONED FOR A FORWARD APPROACH SHALL BE |
| PROVIDED. KNEE AND TOE CLEARANCE COMPLYING WITH 306 |
| SHALL BE PROVIDED. |
| |
| 4D)(2) 2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING |
| SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM |
| AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 5) 2ND REQUEST. SHEETS A3 & A4 ARE MISSING. SHEET A4 |
| THERE IS A DISCREPANCY IN THE WIND SPEEDS; YES THE VULT |
| WIND SPEED FOR THIS WIND ZONE FOR A BUILDING CATEGORY |
| II STRUCTURE IS 170 VULT. THE PLANS GO ONTO INDICATE |
| THE VASD IS 132 WHICH IS ALSO CORRECT. THERE IS ALSO A |
| STATEMENT THE CURRENT NOA?S ARE TOO BE BASED ON 146 |
| VASD. PLEASE NOTE THE 146 VASD WIND ZONES ARE FOR DADE |
| AND BROWARD ONLY. IF THE DESIGNER WISHES TO DESIGN TO |
| THE HIGHER WIND SPEED THEN ALSO UP THE VULT WIND SPEED |
| TO CORRELATE WITH THE 146 VASD. UNTIL THIS IS KNOWN THE |
| PRESSURES GIVEN CANNOT BE DETERMINED FOR CODE |
| COMPLIANCE. PLEASE ALSO NOTE THE PRESSURES GIVEN NOTE |
| MAX. PSF, THIS IS ASSUMED TO BE 10 SQUARE FEET. |
| DISCREPANCY IN PLANS. 107.2.1.3. ALL PRESSURES NEED TO |
| BE EXPRESSED IN VASD SINCE THE PRODUCT APPROVALS ARE IN |
| VASD. |
| |
| 6A) 2ND REQUEST. 2017 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 6B)2ND REQUEST. PLEASE IDENTIFY ON THE PRODUCT APPROVAL |
| BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE |
| SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS |
| WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & |
| HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING |
| SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| THE TESTS. |
| |
| 6C)2ND REQUEST. W. P. B. 107.3.4.1 PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF |
| PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR |
| REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE |
| OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST |
| PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE |
| STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| (561)233-5025 FOR MORE INFORMATION. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |