2018-04-17 07:56:23 | 1ST REVIEW: FBC 2017 6TH EDITION |
| PLUMBING COMMENTS: |
| 1. ACCORDING TO THE BUSINESS TAX RECORDS THE PREVIOUS |
| OCCUPANCY WAS A MERCANTILE WHICH WILL MAKE THIS A |
| CHANGE OF OCCUPANCY AND SHALL COMPLY WITH FBC EX CH 10 |
| 2. PER FBC EX 1006.1 THE REQUIREMENTS OF THE FLORIDA |
| ACCESSIBILITY CODE SHALL BE MET. |
| 3. PLEASE PROVIDE A COST BREAK DOWN TO SHOW WHICH |
| ELEMENTS THAT ARE BEING ALTERED TO COMPLY WITH |
| ACCESSIBILITY TO MEET THE REQUIREMENTS OF FBC ACC |
| 202.4.1DISPROPORTIONATE COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| 4. THE VALUE OF THIS JOB APPEARS LOW WE HAVE SEEN A FEW |
| NEW MICRO BREW PUB COME IN FOR PERMITTING WITH MUCH |
| HIGHER VALUES PLEASE PROVIDE A DETAILED, QUANTITY |
| ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS, VALUE TO |
| INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND |
| DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; |
| EXCLUDING ONLY LAND VALUE. THIS ALSO INCLUDES THE |
| BREWING EQUIPMENT. PER WPB AMEND TO FBC 109.3 |
| 5. PLEASE LABEL ALL BREWING EQUIPMENT AND SHOW LOCATION |
| OF BOILERS AND CHILLERS. PER WPB AMEND TO FBC 107.2.1 |
| 6. PLEASE PROVIDE AN ISOMETRIC DRAWING FOR ALL PROCESS |
| PIPING USED IN BREWING PROCESS. PER WPB AMEND TO FBC |
| 107.3.5.1.3 |
| 7. PLEASE PROVIDE DOMESTIC WATER ISOMETRIC. PER WPB |
| AMEND TO FBC 107.3.5.1.3(13) |
| 8. PLEASE SHOW LOCATION OF THE WATER HEATER AND SHOW |
| COMPLIANCE WITH FBC PL 607.1, 607.2, 607.5 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |