Date |
Text |
2018-04-13 15:35:05 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY |
| NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC |
| 107.3.5 |
| 2. RISER DIAGRAM INDICATES THAT A 2? PVC CONDUIT WILL |
| BE INSTALLED TO FPL TRANSFORMER. FOR THE WIRE SIZE |
| REQUIRED WITH A 400 AMP SERVICE, A 2? PVC IS NOT OF |
| ADEQUATE SIZE. PROVIDE CORRECTION. NEC INFORMATIVE |
| ANNEX C |
| 3. PROVIDE MORE DETAIL FOR RISER DIAGRAM, SHOWING ALL |
| DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD |
| SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30 |
| 4. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS. |
| NEC 110.3, 110.9 |
| 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| 7. SHOW ON PLAN ALL LIGHTING AND POWER BRANCH CIRCUITS |
| EXISTING AND THOSE TO BE INSTALLED. FBC 107.2.1 |
| 8. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 |
| 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 11. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER |
| CODE. NEC 210.64 |
| 12. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| PRESENT. WPB FBC 105.1, 107.2.1 |
| |
| DUE TO EXTENSIVE LACK OF INFORMATION ON PLANS, A |
| COMPLETE REVIEW IS NOT POSSIBLE AT THIS TIME. FURTHER |
| PLAN REVIEW COMMENTS ARE LIKELY. THERE IS A STATEMENT |
| ON THE PLAN IN REFERENCE TO NEC 408.4 THAT APPEARS TO |
| HAVE NO BEARING ON THE DESIGN IN QUESTION. THE |
| DESIGNER?S OPINION OF PLAN REVIEW REQUIREMENTS ASIDE, |
| BE ADVISED THAT NO ?ARM WRESTLING? WILL BE REQUIRED AND |
| THERE WILL BE NO ?WIGGLE ROOM? ON CODE REQUIREMENTS. |
| PROVIDE CORRECTIONS AS NOTED ABOVE. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |