2018-04-07 13:06:35 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE ROOF PLAN. |
| 2. PROVIDE DESIGN WIND LOADS IN ACCORDANCE WITH FBC |
| 2017 SECTION 1609 OR ACSE 7-10 PER PRODUCT APPROVAL |
| LIMITATIONS (PAGE 2 OF 3). |
| 3. PROVIDE FASTENER SPACING BASED ON DESIGN WIND LOADS, |
| (SEE PRODUCT APPROVAL DESIGN UPLIFT PRESSURE), PAGE 2 |
| OF 3. |
| 4. IF METAL PANELS ARE INSTALLED OVER EXISTING |
| SHINGLES, (UNDERLAYMENT OPTION), DESIGNER TO PROVIDE |
| AFFIDAVIT FOR ROOF SHEATHING (MINIMUM DECK ATTACHMENT) |
| AND CERTIFICATION OF EXISTING SHINGLES. |
| 5. DESIGNER TO REVIEW PRODUCT APPROVAL AND APPROVE IN |
| WRITING WITH NAME AND SIGNATURE. |
| |
| FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-R301.2. |
| |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF |
| THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND |
| DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1. |
| WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL |
| MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING, |
| THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH |
| PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE |
| WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR |
| HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED |
| TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR |
| WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR |
| WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN |
| GARAGE DOORS). |
| |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, REVIEW ROOFING SUBMITTALS. |
| |
| |
| |
| FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5) AND F.S. 481.229. |
| |
| |
| |
| |