Plan Review Notes
Plan Review Notes For Permit 18031309
Permit Number 18031309
Review Stop P
Sequence Number 1
Notes
Date Text
2018-04-13 15:03:291) SHT. A100 - FIXTURE ELEVATIONS & ELEV. #01- THE
 TOILET PAPER DISPENSER SHALL BE LOCATED A MINIMUM OF 7
 INCHES AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER AND
 THE OUTLET SHALL BE A MINIMUM OF 14 INCHES AND A
 MAXIMUM OF 19 INCHES ABOVE THE FINISH FLOOR. 2017
 FBC-ACCESS. SEC. 604.9.6.
 2) SHT. A100 - ELEVATIONS #01 & #02 - THE GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE,
 NOT TO THE CENTER. 2017 FBC-ACCESS. SEC.609.4.
 3) SHT. A100 - ELEV. #02 - THE OPERABLE PARTS OF THE
 HAND DRYER AND THE SANITARY NAPKIN DISPENSER SHALL BE
 LOCATED A MAXIMUM OF 48 INCHES ABOVE THE FINISH FLOOR
 PER 2017 FBC-ACCESS. SECS. 308 & 309.
 4) SHOW THE CLEAR INSIDE DIMENSIONS ( LENGTH X WIDTH)
 OF THE NEW TOILET ROOM. IN ADDITION, SHOW THE CLEAR
 FLOOR SPACE DIMENSIONS FOR THE WATER CLOSET AND THE
 LAVATORY. COMPLY WITH 2017 FBC-ACCESS. SECS.604.3 AND
 606.2.
 5) SHOW THE SIZE OF THE EXPANSION TANK FOR THE WATER
 HEATER. THE SIZE OF THE EXPANSION TANK SHALL BE SIZED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.2017
 FBC-PLUMBING SEC. 607.3.
 6) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN BOTH
 TOILET ROOMS PER THE 2017 FBC-PLUMBING SEC.416.5.
 TEMPERED WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B 125.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  