Date |
Text |
2018-04-13 15:03:29 | 1) SHT. A100 - FIXTURE ELEVATIONS & ELEV. #01- THE |
| TOILET PAPER DISPENSER SHALL BE LOCATED A MINIMUM OF 7 |
| INCHES AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER |
| CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER AND |
| THE OUTLET SHALL BE A MINIMUM OF 14 INCHES AND A |
| MAXIMUM OF 19 INCHES ABOVE THE FINISH FLOOR. 2017 |
| FBC-ACCESS. SEC. 604.9.6. |
| 2) SHT. A100 - ELEVATIONS #01 & #02 - THE GRAB BARS |
| SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE, |
| NOT TO THE CENTER. 2017 FBC-ACCESS. SEC.609.4. |
| 3) SHT. A100 - ELEV. #02 - THE OPERABLE PARTS OF THE |
| HAND DRYER AND THE SANITARY NAPKIN DISPENSER SHALL BE |
| LOCATED A MAXIMUM OF 48 INCHES ABOVE THE FINISH FLOOR |
| PER 2017 FBC-ACCESS. SECS. 308 & 309. |
| 4) SHOW THE CLEAR INSIDE DIMENSIONS ( LENGTH X WIDTH) |
| OF THE NEW TOILET ROOM. IN ADDITION, SHOW THE CLEAR |
| FLOOR SPACE DIMENSIONS FOR THE WATER CLOSET AND THE |
| LAVATORY. COMPLY WITH 2017 FBC-ACCESS. SECS.604.3 AND |
| 606.2. |
| 5) SHOW THE SIZE OF THE EXPANSION TANK FOR THE WATER |
| HEATER. THE SIZE OF THE EXPANSION TANK SHALL BE SIZED |
| IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.2017 |
| FBC-PLUMBING SEC. 607.3. |
| 6) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN BOTH |
| TOILET ROOMS PER THE 2017 FBC-PLUMBING SEC.416.5. |
| TEMPERED WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B 125.3. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |