 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18031303
 ADD: 911 ALMERIA RD.
 CONT: J & V RESIDENTIAL SERVICES
 TEL: 561-601-1614
 E-MAIL: JVRESIDENTIAL [email protected]
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 1ST REVIEW
 DATE: FRI. MARCH 30, 2018
 ACTION: BUILDING PROVISO
 1) SLOPE 3 ? IN 12. PLEASE SHOW COMPLIANCE WITH 2017
 FBC-B TABLE 1507.1.1.
  
 1. 1.ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (17-PERCENT SLOPE), AND LESS THAN FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 APPLY A 19-INCH (483 MM) STRIP OF UNDERLAYMENT FELT
 PARALLEL TO AND STARTING AT THE EAVES, FASTENED
 SUFFICIENTLY TO HOLD IN PLACE. STARTING AT THE EAVE,
 APPLY 36-INCHWIDE (914 MM) SHEETS OF UNDERLAYMENT,
 OVERLAPPING SUCCESSIVE SHEETS 19 INCHES (483 MM), END
 LAPS SHALL BE 6 INCHES AND SHALL BE OFFSET BY 6 FEET.
 THE UNDERLAYMENT SHALL BE ATTACHED TO A NAILABLE DECK
 WITH CORROSION-RESISTANT FASTENERS WITH ONE ROW
 CENTERED IN THE FIELD OF THE SHEET WITH A MAXIMUM
 FASTENER SPACING OF 12 INCHES (305 MM) O.C., AND ONE
 ROW AT THE END AND SIDE LAPS FASTENED 6 INCHES (152 MM)
 O.C. UNDERLAYMENT SHALL BE ATTACHED USING METAL OR
 PLASTIC CAP NAILS WITH A NOMINAL CAP DIAMETER OF NOT
 LESS THAN 1 INCH. METAL CAPS SHALL HAVE A THICKNESS OF
 NOT LESS THAN 32-GAGE SHEET METAL. POWER-DRIVEN METAL
 CAPS SHALL HAVE A MINIMUM THICKNESS OF 0.010 INCH.
 MINIMUM THICKNESS OF THE OUTSIDE EDGE OF PLASTIC CAPS
 SHALL BE 0.035 INCH. THE CAP NAIL SHANK SHALL BE NOT
 LESS THAN 0.083 INCH FOR RING SHANK CAP NAILS AND 0.091
 INCH FOR SMOOTH SHANK CAP NAILS. CAP NAIL SHANK SHALL
 HAVE A LENGTH SUFFICIENT TO PENETRATE THROUGH THE ROOF
 SHEATHING OR NOT LESS THAN 3/4 INCH INTO THE ROOF
 SHEATHING.
 2. 2.ROOF SLOPES OF FOUR UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (33-PERCENT SLOPE) OR GREATER. UNDERLAYMENT
 SHALL BE APPLIED SHINGLE FASHION, PARALLEL TO AND
 STARTING FROM THE EAVE AND LAPPED 4 INCHES (51 MM), END
 LAPS SHALL BE 6 INCHES AND SHALL BE OFFSET BY 6 FEET.
 THE UNDERLAYMENT SHALL BE ATTACHED TO A NAILABLE DECK
 WITH TWO STAGGERED ROWS IN THE FIELD OF THE SHEET WITH
 A MAXIMUM FASTENER SPACING OF 12 INCHES (305 MM) O.C.,
 AND ONE ROW AT THE END AND SIDE LAPS FASTENED 6 INCHES
 (152 MM) O.C. UNDERLAYMENT SHALL BE ATTACHED USING
 METAL OR PLASTIC CAP NAILS WITH A NOMINAL CAP DIAMETER
 OF NOT LESS THAN 1 INCH. METAL CAPS SHALL HAVE A
 THICKNESS OF NOT LESS THAN 32-GAGE SHEET METAL.
 POWER-DRIVEN METAL CAPS SHALL HAVE A MINIMUM THICKNESS
 OF 0.010 INCH. MINIMUM THICKNESS OF THE OUTSIDE EDGE OF
 PLASTIC CAPS SHALL BE 0.035 INCH. THE CAP NAIL SHANK
 SHALL BE NOT LESS THAN 0.083 INCH FOR RING SHANK CAP
 NAILS AND 0.091 INCH FOR SMOOTH SHANK CAP NAILS. CAP
 NAIL SHANK SHALL HAVE A LENGTH SUFFICIENT TO PENETRATE
 THROUGH THE ROOF SHEATHING OR NOT LESS THAN 3/4 INCH
 INTO THE ROOF SHEATHING.
 3. 3.ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (17-PERCENT SLOPE), AND GREATER. THE ENTIRE
 ROOF DECK SHALL BE COVERED WITH AN APPROVED
 SELF-ADHERING POLYMER MODIFIED BITUMEN UNDERLAYMENT
 COMPLYING WITH ASTM D1970 INSTALLED IN ACCORDANCE WITH
 BOTH THE UNDERLAYMENT MANUFACTURER?S AND ROOF COVERING
 MANUFACTURER?S INSTALLATION INSTRUCTIONS FOR THE DECK
 MATERIAL, ROOF VENTILATION CONFIGURATION AND CLIMATE
 EXPOSURE FOR THE ROOF COVERING TO BE INSTALLED.
 EXCEPTION: A MINIMUM 4-INCH-WIDE (102 MM) STRIP OF
 SELF-ADHERING POLYMER-MODIFIED BITUMEN MEMBRANE
 COMPLYING WITH ASTM D1970, INSTALLED IN ACCORDANCE WITH
 THE MANUFACTURER?S INSTRUCTIONS FOR THE DECK MATERIAL,
 SHALL BE APPLIED OVER ALL JOINTS IN THE ROOF DECKING.
 AN APPROVED UNDERLAYMENT IN ACCORDANCE WITH TABLE
 1507.1.1 FOR THE APPLICABLE ROOF COVERING SHALL BE
 APPLIED OVER THE ENTIRE ROOF OVER THE 4-INCH-WIDE (102
 MM) MEMBRANE STRIPS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER/ BUILDING
 DIVISION / DEVELOPMENT SERVICES DEPART
  