Plan Review Notes
Plan Review Notes For Permit 18031284
Permit Number 18031284
Review Stop M
Sequence Number 2
Notes
Date Text
2018-07-05 09:12:27PASS PROVISO
 1) REFER TO SECTION 603.3 DETECTORS SHALL MONITOR THE
 INTIRE AIRFLOW
 ACCESS DOORS REQUIRED. 2017 FBC (M)
 2) REFER TO SECTION 606.2.1 DETECTORS MUST BE INSTALLED
 ON THE SUPPLY
 SIDE OF AIR FLOW. 2017 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER