Plan Review Notes For Permit 18031284 |
Permit Number |
18031284 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-06-27 11:33:05 | PERMIT #18031284 | | REVIEW COMMENTS | | | | 1) ADDITIONAL HORN STROBE REQUIRED IN MEETING ROOM | | AREA. (MARKED ON PLAN FOR REFERENCE.) | | | | 2) PLEASE NOTE THAT AT NO POINT WERE ADDITIONAL SMOKE | | DETECTORS REQUESTED OR REQUIRED BY THE AHJ, AS | | INCORRECTLY NOTED IN RESUBMISSION NOTES BY CONTRACTOR. | | THE INITIAL REVIEW COMMENTS SPECIFICALLY STATED | | "AUDIO/VISUAL DEVICES". | | | | SUE ELLEN CALDERON | | ASST. FIRE MARSHAL | | WPBFR | | [email protected] | | |
|