2018-05-22 06:47:08 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| |
| |
| 1) FROM PREVIOUS LIST: 2014 FBC-B 1009.9.3 ENCLOSURES |
| UNDER INTERIOR STAIRWAYS. THE WALLS AND SOFFITS WITHIN |
| ENCLOSED USABLE SPACES UNDER ENCLOSED AND UNENCLOSED |
| STAIRWAYS SHALL BE PROTECTED BY 1-HOUR |
| FIRE-RESISTANCE-RATED CONSTRUCTION OR THE |
| FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE, |
| WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED SPACE |
| SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR ENCLOSURE. |
| |
| 2ND REVIEW: PLANS HAVE BEEN REVISED TO SPECIFY UL263. |
| THIS ASSEMBLY IS FOR USE AS A WALL ONLY; REVISE PLAN TO |
| SPECIFY CEILING. |
| |
| 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| |