Notes |
Date |
Text |
2018-04-02 15:42:09 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS OF FIRE SPRINKLER WORK | | UNDER SEPARATE SHOP DRAWINGS. | | | | PLEASE PROVIDE AN APPLICBALE NOTE. | | | | | | 2) THERE ARE NO INDICATION THAT THE CEILING OF THE ROOM | | UNDER THE INTERIOR EXIT STAIRS ARE RATED PER NFPA 101, | | CHAPTER 7. | | | | 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED | | UNDER STAIRS, | | PROVIDED THAT BOTH ALL OF THE FOLLOWING CRITERIA ARE | | MET: | | (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR | | ENCLOSURE BY THE | | SAME FIRE RESISTANCE AS THE EXIT ENCLOSURE. | | (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE | | FROM | | WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.) | | (3) THE SPACE IS NOT USED FOR THE STORAGE OF | | COMBUSTIBLE OR | | FLAMMABLE LIQUIDS, OR OTHERWISE HAZARDOUS MATERIALS. | | | | PLEASE PROVIDE DETAILS. | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|