2018-03-30 08:38:52 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE LOAD CALCULATION FOR SERVICE AT WIREWAY #3, |
| INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| EC 405.7.1 |
| 3. A CONFLICT EXIST ON SHEET E3.1. TRANSFORMER GROUND |
| NOTES STATE A # 6 GROUND SHOULD BE RUN TO BUILDING |
| STEEL, WHILE THE FEEDER SIZE KEY NOTES STATES THAT A # |
| 2 SHOULD BE RUN. PROVIDE CORRECTION. FBC 107.2.1; NEC |
| 250.30 |
| 4. VALUE STATED FOR THE INCREASE IN WORK APPEARS LOW. |
| PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF |
| WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 |
| 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |