Plan Review Notes
Plan Review Notes For Permit 18031260
Permit Number 18031260
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-30 15:23:142014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 18031260
 W. P. B. PERMIT: 17100783
 ADD: 480 HIBISCUS ST. SUITE: 115
 CONT: IBS CONSTRUCTION
 TEL: 305-527-8303
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 30/ 2018
 ACTION: DENIED
  
 1) SHEET A201 SHOWS (2) ROOMS BEING BUILT UNDERNEATH
 THE MEZZANINE STAIRS. ROOMS 103 AND ROOM 104. PLEASE
 SHOW COMPLIANCE WITH;
 2014 FBC-B 1009.9.3 ENCLOSURES UNDER INTERIOR
 STAIRWAYS. THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE
 SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR
 ENCLOSURE.
  
 2) SHEET A202 AND A901 SHOW DETAILS OF THE USE FOR
 GLASS CEILINGS, GL9 & GL10. PLEASE PROVIDE HOW
 COMPLIANCE WILL BE ACHIEVED WITH EITHER SECTION:
 2014 FBC-B 2405.2 ALLOWABLE GLAZING MATERIALS AND
 LIMITATIONS. SLOPED GLAZING SHALL BE ANY OF THE
 FOLLOWING MATERIALS, SUBJECT TO THE LISTED LIMITATIONS.
 OR
 2014 FBC-B 2606.1. THE PROVISIONS OF THIS SECTION AND
 SECTIONS 2607 THROUGH 2611 SHALL GOVERN THE QUALITY AND
 METHODS OF APPLICATION OF LIGHT-TRANSMITTING PLASTICS
 FOR USE AS LIGHT-TRANSMITTING MATERIALS IN BUILDINGS
 AND STRUCTURES. FOAM PLASTICS SHALL COMPLY WITH SECTION
 2603. LIGHT-TRANSMITTING PLASTIC MATERIALS THAT MEET
 THE OTHER CODE REQUIREMENTS FOR WALLS AND ROOFS SHALL
 BE PERMITTED TO BE USED IN ACCORDANCE WITH THE OTHER
 APPLICABLE CHAPTERS OF THE CODE.
  
 3) SHEET A901 SHOWS GLASS PANEL SECTIONS GL 01 THRIUGH
 GL 08. THERE ARE NO DETAILS INDICATING THE TYPE OF
 GLAZING, THICKNESS OF GLAZING IN EITHER THE DOOR, AND
 OR SIDELIGHTS NEXT TO THE DOOR. PLEASE REVIEW SECTION
 2406.4OF THE FBC-B, HAZARDOUS LOCATIONS. THE LOCATIONS
 SPECIFIED IN SECTIONS 2406.4.1 THROUGH 2406.4.7 SHALL
 BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS REQUIRING
 SAFETY GLAZING MATERIALS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved