2018-11-06 17:37:332ND REVIEW FBC-2010 MECHANICAL
 PERMIT #18031052
 11/6/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CALCULATION PRINTOUT IS INDICATING MIAMI AS
 THE PROJECT LOCATION. PLEASE PROVIDE CALCULATIONS USING
 THE CORRECT LOCATION, AND INCLUDE THE ADDRESS AND UNIT
 NUMBER ON THE CALCULATION PRINTOUT.
  
 2) M2.1: SMOKE DETECTORS ARE REQUIRED IN BOTH THE
 SUPPLY AND THE RETURN SYSTEMS OF THE HP'S- SECTION
 606.2 FBC M.
  
 3) M2.1: PROVIDE THE RETURN OPENING DIMENSIONS AT EACH
 HP CLOSET- SECTION 601.4 FBC M.
  
 4) M2.1: THERE IS INSUFFICENT INFORMATION AND DETAILS
 ON THE PLAN TO SHOW COMPLIANCE FOR THE REQUIRED KITCHEN
 EXHAUST SYSTEMS:
  
 A) PLEASE PROVIDE ENLARGED KITCHEN EXHAUST DETAILS ON
 THE PLAN SHOWING THE COOKTOP DOWNDRAFT EXHAUST DUCT
 RUNS AND TERMINATION LOCATIONS. CLARIFY IF TWO SYSTEMS
 WILL BE INSTALLED- ONE FOR THE GAS-FIRED COOKTOP AND
 ONE FOR THE ELECTRIC COOKTOP. SPECS HAVE BEEN SUBMITTED
 FOR EACH HOWEVER THE PLAN APPEARS TO SHOW ONLY ONE
 COOKTOP.
  
 B) THE COMB-OVEN, SPEED OVEN, AND CONVECTION OVEN EACH
 REQUIRE AN EXHAUST VENTILATION SYSTEM HOWEVER NO SPECS
 FOR THE VENTS HAVE BEEN SUBMITTED AND NO DETAILS HAVE
 BEEN PROVIDED ON THE PLAN.
  
 C) PLEASE REFER TO TABLE 403.3 WHICH REQUIRES AN
 EXHAUST VENTILATION RATE OF 25 CFMS PER SF. FOR
 CONTINUOUS VENTILATION, AND 100 CFMS PER SF. FOR
 INTERMITTENT VENTILATION.
  
 5) THE DRYER BOOSTER FAN SPECS DO NOT INDICATE THE FAN
 IS LISTED AND LABELED FOR USE WITH A CLOTHES DRYER-
 SECTION 504.6.4.1 FBC M
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  