2018-09-05 17:04:27 | 1ST REVIEW FBC-2010 MECHANICAL |
| PERMIT #18031052 |
| 9/5/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| PLEASE NOTE THAT ALL APARTMENT BUILDOUTS WILL BE |
| DESIGNED UNDER THE 2010 FLORIDA BUILDING CODES UNTIL |
| WHICH TIME THE ENTIRE BUILDING RECEIVES A CERTIFICATE |
| OF OCCUPANCY. |
| |
| 1) PLEASE REPLACE THE ENERGYGAUGE 2017 COMPLIANCE |
| SUBMITTAL WITH THE 2010 VERSION AND PROVIDE PIPING |
| SYSTEM COMPLIANCE DATA THAT IS MISSING FROM THE FORM. |
| |
| 2) M2.1: SHOW THE LOCATION OF THE O/A DUCT THAT IS |
| SUPPLYING THE UNITS VIA THE RETURN AIR PLENUM, |
| |
| 3) M2.1: DUE TO THE FACT THAT THE AC CLOSETS ARE |
| SHARING A COMMON PLENUM SMOKE DETECTORS SHALL BE |
| PROVIDED IN THE RETUN AIR PLENUM IN ACCORDANCE WITH |
| SECTION 606.2.2 FBC M. |
| |
| 4) M2.1: REGARDING THE INTUMESCENT PAINT ON THE AC |
| CLOSET DOORS, IT HAS BEEN DETERMINED THAT THE ENGINEER |
| OF RECORD SHALL BE RESPONSIBLE FOR INSPECTING AND |
| CERTIFYING THE APPLICATION PROCESS. PLACE A NOTE ON THE |
| PLAN ACCORDINGLY. |
| |
| 5) M2.1: THE RESPONSE NARRATIVE FROM THE JOHNSON GROUP |
| IS REFERENCING SHEET AXX FOR THE DRYER ENCLOSURE |
| DETAIL. I WAS NOT ABLE TO LOCATE THE SHEET OR DETAIL. |
| |
| 6) M2.1: THE RESPONSE NARRATIVE FROM THE JOHNSON GROUP |
| IS REFERENCING A DIMENSIONED, SEGMENTED DRAWING OF THE |
| DRYER EXHAUST DUCT WHICH I WAS UNABLE TO LOCATE. PLEASE |
| PROVIDE THE DRAWING. |
| |
| 7) M2.1 : CLARIFY THE NEED FOR THE DRYER EXHAUST |
| BOOSTER FAN. PER THE EQUIVALENT LENGTH TABLE, THE 120 |
| FT. RUN DOES NOT EXCEED THE 125 FT. MAXIMUM RUN ALLOWED |
| BY THE MANUFACTURER. IN ADDITION, PLEASE CONTACT FIRE |
| CHIEF PETER LEDUC FOR PERMISSION TO INSTALL THE BOOSTER |
| FAN. IF PERMITTED, AN ACCESS PANEL WILL BE REQUIRED FOR |
| SERVICE AND REPLACEMENT OF THE FAN- SECTION 306.1. |
| |
| 8) M2.1: THE COMBUSTION AIR CALCULATION TABLE LISTS THE |
| KITCHEN AT 3860 SQ. FT. WHICH CLEARLY FROM THE DRAWINGS |
| IT IS NOT. PLEASE PROVIDE AN ACCURATE CALCULATION. |
| |
| 9) THE REQUESTED PRODUCT DATA SHEETS FOR THE GAS FIRED |
| APPLIANCES AND DOWN DRAFT EXHAUST SYSTEM WERE NOT |
| PROVIDED. PLEASE NOTE THAT AN EXHAUST HOOD MAY BE |
| REQUIRED FOR THE OVENS PER SECTION 507.2.2 FBC M. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |