2018-09-05 17:04:271ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18031052
 9/5/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE NOTE THAT ALL APARTMENT BUILDOUTS WILL BE
 DESIGNED UNDER THE 2010 FLORIDA BUILDING CODES UNTIL
 WHICH TIME THE ENTIRE BUILDING RECEIVES A CERTIFICATE
 OF OCCUPANCY.
  
 1) PLEASE REPLACE THE ENERGYGAUGE 2017 COMPLIANCE
 SUBMITTAL WITH THE 2010 VERSION AND PROVIDE PIPING
 SYSTEM COMPLIANCE DATA THAT IS MISSING FROM THE FORM.
  
 2) M2.1: SHOW THE LOCATION OF THE O/A DUCT THAT IS
 SUPPLYING THE UNITS VIA THE RETURN AIR PLENUM,
  
 3) M2.1: DUE TO THE FACT THAT THE AC CLOSETS ARE
 SHARING A COMMON PLENUM SMOKE DETECTORS SHALL BE
 PROVIDED IN THE RETUN AIR PLENUM IN ACCORDANCE WITH
 SECTION 606.2.2 FBC M.
  
 4) M2.1: REGARDING THE INTUMESCENT PAINT ON THE AC
 CLOSET DOORS, IT HAS BEEN DETERMINED THAT THE ENGINEER
 OF RECORD SHALL BE RESPONSIBLE FOR INSPECTING AND
 CERTIFYING THE APPLICATION PROCESS. PLACE A NOTE ON THE
 PLAN ACCORDINGLY.
  
 5) M2.1: THE RESPONSE NARRATIVE FROM THE JOHNSON GROUP
 IS REFERENCING SHEET AXX FOR THE DRYER ENCLOSURE
 DETAIL. I WAS NOT ABLE TO LOCATE THE SHEET OR DETAIL.
  
 6) M2.1: THE RESPONSE NARRATIVE FROM THE JOHNSON GROUP
 IS REFERENCING A DIMENSIONED, SEGMENTED DRAWING OF THE
 DRYER EXHAUST DUCT WHICH I WAS UNABLE TO LOCATE. PLEASE
 PROVIDE THE DRAWING.
  
 7) M2.1 : CLARIFY THE NEED FOR THE DRYER EXHAUST
 BOOSTER FAN. PER THE EQUIVALENT LENGTH TABLE, THE 120
 FT. RUN DOES NOT EXCEED THE 125 FT. MAXIMUM RUN ALLOWED
 BY THE MANUFACTURER. IN ADDITION, PLEASE CONTACT FIRE
 CHIEF PETER LEDUC FOR PERMISSION TO INSTALL THE BOOSTER
 FAN. IF PERMITTED, AN ACCESS PANEL WILL BE REQUIRED FOR
 SERVICE AND REPLACEMENT OF THE FAN- SECTION 306.1.
  
 8) M2.1: THE COMBUSTION AIR CALCULATION TABLE LISTS THE
 KITCHEN AT 3860 SQ. FT. WHICH CLEARLY FROM THE DRAWINGS
 IT IS NOT. PLEASE PROVIDE AN ACCURATE CALCULATION.
  
 9) THE REQUESTED PRODUCT DATA SHEETS FOR THE GAS FIRED
 APPLIANCES AND DOWN DRAFT EXHAUST SYSTEM WERE NOT
 PROVIDED. PLEASE NOTE THAT AN EXHAUST HOOD MAY BE
 REQUIRED FOR THE OVENS PER SECTION 507.2.2 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER