2018-05-09 10:18:37 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18031052 |
| 4/9/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M2.1: THE SE-2 DUCT IS NOT PERMITTED TO |
| PENETRATE INTO THE INTERIOR STAIRWELL ENCLOSURE- |
| SECTION 1023.5 FBC-17 BUILDING. |
| |
| 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| HEAT PUMPS. THE CALCULATIONS SUBMITTED UNDER THE MAIN |
| BUILDING PERMIT ARE NOT VALID FOR THIS NEW INTERIOR |
| BUILDOUT UNDER NEW OWNERSHIP AND SEPARATE PERMIT - |
| SECTION C403.2.1 FBC-17 ENERGY CONSERVATION. |
| |
| 3) PROVIDE AN ENERGY COMPLIANCE REPORT. THE |
| CALCULATIONS SUBMITTED UNDER THE MAIN BUILDING PERMIT |
| ARE NOT VALID FOR THIS NEW INTERIOR BUILDOUT UNDER NEW |
| OWNERSHIP AND SEPARATE PERMIT SECTION C101.5 |
| |
| 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE |
| SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE |
| HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY |
| CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY |
| CONSERVATION. CLARIFY HOW O/A IS BEING SUPPLIED TO THE |
| HEAT PUMPS. |
| |
| 7) M2.1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE |
| SUPPLY SYSTEM OF HP-G- SECTION 606.2.1. THIS |
| REQUIREMENT MAY BE WAIVED IF MANUFACTURER'S |
| SPECIFICATIONS INDICATE THE UNIT CANNOT PRODUCE OVER |
| 2000 CFMS OF SUPPLY AIR. |
| |
| 8) M2.1 & A9.1: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR |
| THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17 |
| MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION. |
| |
| 10) M2.1: DRYER: A) PER NOTES #12 & 26 : PROVIDE |
| CONSTRUCTION DETAILS OR MANUFACTURER'S SPECIFICATIONS |
| FOR THE DRYER EXHAUST DUCT PLENUM ENCLOSURE- SECTION |
| 504.4. B) SUBMIT MANUFACTURER' SPECIFICATIONS FOR THE |
| DRYER THAT LISTS THE MAXIMUM LENGTH OF THE EXHAUST DUCT |
| RUN- 504.8.4. C) PROVIDE A DRAWING THAT SHOWS THE TOTAL |
| RUN LENGTH OF THE EXHAUST DUCT FROM THE DRYER OUTLET |
| |
| TO THE SHAFT INCLUDING SEGMENTED LENGTH MEASUREMENTS, |
| AND THE EQUIVALENT LENGTHS OF THE ELBOWS- 504.8.4. D) |
| INDICATE WHICH SUBDUCT DETAIL ON SHEET M2.4 IS |
| APPLICABLE TO THE DRYER EXHAUST. E) PROVIDE MAKEUP AIR |
| FOR THE DRYER PER SECTION 504.6. |
| |
| 11) M2.1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| COOKTOPS, THE OVENS, AND THE RECIRCULATING DOWN DRAFT |
| EXHAUST SYSTEMS. NO HOODS ARE SHOWING ON THE PLANS FOR |
| THE OVENS, HOWEVER THEY MAY BE REQUIRED PER |
| MANUFACTURER'S SPECIFICATIONS. PLEASE NOTE THAT |
| COMMERCIAL COOKING APPLIANCES ARE NOT PERMITTED FOR USE |
| IN DWELLING UNITS- SECTION 917.2 FBC-17 MECHANICAL, AND |
| |
| 623.3 FBC-17 FUEL GAS. |
| |
| 12) M2.1 FOR GAS-FIRED COOKING APPLIANCES, INDICATE HOW |
| COMBUSTION AIR IS BEING PROVIDED AND PROVIDE |
| CALCULATIONS- SECTION 304 FBC-17 FUEL GAS. |
| |
| 13) M2.1, MASTER BATH 133: THE PLAN DOES NOT CLEARLY |
| SHOW HOW THE EXHAUST SYSTEMS ARE WORKING IN BATHS 134A |
| AND 135A. IT APPEARS THAT THE EF-B'S ARE CONNECTING TO |
| THE RETURN AIR PLENUM PER NOTE #6 , HOWEVER NOTE #23 |
| INDICATES THE RETURN GRILLS ARE PROVIDED OUTDOOR AIR. |
| A) REFER TO FOOTNOTE G TABLE 403.3 WHICH LIMITS |
| RECIRCULATION OF AIR FROM THE BATHROOMS TO 10% OF THE |
| TOTAL |
| |
| SUPPLY AIR PROVIDED TO THE SPACES. THE PLAN APPEARS TO |
| INDICATE NON-COMPLIANCE. |
| |
| 14) M2.1: EXHAUST IS REQUIRED FOR BATHROOMS 119B, 120B, |
| AND 121B. THE PLAN SHOWS EXHAUST PROVIDED ONLY FOR THE |
| SHOWERS. |
| |
| 15) M2.4: PLEASE INDICATE WHICH OF THE SUBDUCT DETAILS |
| IS FOR THE TOILET EXHAUST. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |