Plan Review Notes
Plan Review Notes For Permit 18031052
Permit Number 18031052
Review Stop M
Sequence Number 1
Notes
Date Text
2018-05-09 10:18:371ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18031052
 4/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: THE SE-2 DUCT IS NOT PERMITTED TO
 PENETRATE INTO THE INTERIOR STAIRWELL ENCLOSURE-
 SECTION 1023.5 FBC-17 BUILDING.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 HEAT PUMPS. THE CALCULATIONS SUBMITTED UNDER THE MAIN
 BUILDING PERMIT ARE NOT VALID FOR THIS NEW INTERIOR
 BUILDOUT UNDER NEW OWNERSHIP AND SEPARATE PERMIT -
 SECTION C403.2.1 FBC-17 ENERGY CONSERVATION.
  
 3) PROVIDE AN ENERGY COMPLIANCE REPORT. THE
 CALCULATIONS SUBMITTED UNDER THE MAIN BUILDING PERMIT
 ARE NOT VALID FOR THIS NEW INTERIOR BUILDOUT UNDER NEW
 OWNERSHIP AND SEPARATE PERMIT SECTION C101.5
  
 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE
 HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY
 CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION. CLARIFY HOW O/A IS BEING SUPPLIED TO THE
 HEAT PUMPS.
  
 7) M2.1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY SYSTEM OF HP-G- SECTION 606.2.1. THIS
 REQUIREMENT MAY BE WAIVED IF MANUFACTURER'S
 SPECIFICATIONS INDICATE THE UNIT CANNOT PRODUCE OVER
 2000 CFMS OF SUPPLY AIR.
  
 8) M2.1 & A9.1: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR
 THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17
 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION.
  
 10) M2.1: DRYER: A) PER NOTES #12 & 26 : PROVIDE
 CONSTRUCTION DETAILS OR MANUFACTURER'S SPECIFICATIONS
 FOR THE DRYER EXHAUST DUCT PLENUM ENCLOSURE- SECTION
 504.4. B) SUBMIT MANUFACTURER' SPECIFICATIONS FOR THE
 DRYER THAT LISTS THE MAXIMUM LENGTH OF THE EXHAUST DUCT
 RUN- 504.8.4. C) PROVIDE A DRAWING THAT SHOWS THE TOTAL
 RUN LENGTH OF THE EXHAUST DUCT FROM THE DRYER OUTLET
  
 TO THE SHAFT INCLUDING SEGMENTED LENGTH MEASUREMENTS,
 AND THE EQUIVALENT LENGTHS OF THE ELBOWS- 504.8.4. D)
 INDICATE WHICH SUBDUCT DETAIL ON SHEET M2.4 IS
 APPLICABLE TO THE DRYER EXHAUST. E) PROVIDE MAKEUP AIR
 FOR THE DRYER PER SECTION 504.6.
  
 11) M2.1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 COOKTOPS, THE OVENS, AND THE RECIRCULATING DOWN DRAFT
 EXHAUST SYSTEMS. NO HOODS ARE SHOWING ON THE PLANS FOR
 THE OVENS, HOWEVER THEY MAY BE REQUIRED PER
 MANUFACTURER'S SPECIFICATIONS. PLEASE NOTE THAT
 COMMERCIAL COOKING APPLIANCES ARE NOT PERMITTED FOR USE
 IN DWELLING UNITS- SECTION 917.2 FBC-17 MECHANICAL, AND
  
 623.3 FBC-17 FUEL GAS.
  
 12) M2.1 FOR GAS-FIRED COOKING APPLIANCES, INDICATE HOW
 COMBUSTION AIR IS BEING PROVIDED AND PROVIDE
 CALCULATIONS- SECTION 304 FBC-17 FUEL GAS.
  
 13) M2.1, MASTER BATH 133: THE PLAN DOES NOT CLEARLY
 SHOW HOW THE EXHAUST SYSTEMS ARE WORKING IN BATHS 134A
 AND 135A. IT APPEARS THAT THE EF-B'S ARE CONNECTING TO
 THE RETURN AIR PLENUM PER NOTE #6 , HOWEVER NOTE #23
 INDICATES THE RETURN GRILLS ARE PROVIDED OUTDOOR AIR.
 A) REFER TO FOOTNOTE G TABLE 403.3 WHICH LIMITS
 RECIRCULATION OF AIR FROM THE BATHROOMS TO 10% OF THE
 TOTAL
  
 SUPPLY AIR PROVIDED TO THE SPACES. THE PLAN APPEARS TO
 INDICATE NON-COMPLIANCE.
  
 14) M2.1: EXHAUST IS REQUIRED FOR BATHROOMS 119B, 120B,
 AND 121B. THE PLAN SHOWS EXHAUST PROVIDED ONLY FOR THE
 SHOWERS.
  
 15) M2.4: PLEASE INDICATE WHICH OF THE SUBDUCT DETAILS
 IS FOR THE TOILET EXHAUST.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER