2018-05-16 11:43:431ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-2.2 SHOWS THE G/# RISER 3/4 NG TO UNIT SHOWS
 104 CFH THE TOTAL BTU LOAD ON THE ISOMETRIC IS ONLY 66
 CFH PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT P-2.2 SHOWS THE PIPING TO THE DRYER AS 1/2" THE
 ISOMETRIC ON SHT P-3.1 SHOWS 3/4" PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304
  
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC.
 402.2 ALSO PROVIDE INSTALLATION GUIDE FOR DRYER VENT.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  