2018-04-06 15:21:08 | ****PLAN REVIEW COMMENTS**** |
| |
| ART LANGE BUILDING PLANS EXAMINER |
| |
| DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33402 |
| |
| 561-805-6718 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| 2017 6TH EDITION |
| |
| 1. FAIR HOUSING DESIGN MANUAL |
| |
| A) KITCHEN ISLAND DOES NOT HAVE 40 INCH CLEARANCE ON |
| TWO SIDES. |
| |
| B. PROVIDE 32 INCHES CLEAR AT BATHROOM DOORS. |
| |
| C. IN THE FAIR HOUSING DESIGN MANUAL CHAPTER 7 SELECT |
| WHETHER YOU WILL BE USING A OR B SPECIFICATIONS WHEN |
| DESIGNING THE BATHROOMS. SHOW THIS ON THE PLANS AND |
| ADJUST LAYOUT ACCORDINGLY. |
| |
| 2. DOORS |
| |
| A. DOOR 111 NOT SHOWN ON SCHEDULE. |
| |
| B. PROVIDE INFORMATION ON DOOR 101C. ROLL DOWN SMOKE |
| DOOR IF USED. NOTE, SINCE THE ELEVATOR IS PRESSURIZED |
| THIS DOOR IS NOT REQUIRED. |
| |
| 3. PROVIDE UNDERLAYMENT USED FOR WOOD FLOOR IN ROOM |
| 121A GYM. IF PLYWOOD UNDERLAYMENT IS USED SHOW |
| COMPLIANCE WITH FBC 603.1 COMBUSTIBLE MATERIALS. |
| |
| 4. PROVIDE THE FOLLOWING FLOOR UNDERLAYMENT SOUND |
| PROOFING INFORMATION. |
| |
| STRUCTURAL BORNE SOUND TEST HAS BEEN RECEIVED. |
| |
| SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR |
| COMPLIANCE WITH THE 2010 FBC-B SECTIONS: |
| |
| FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FBC-B 2010 1207.2 AIR-BORNE SOUND. |
| FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE |
| SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS |
| SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE |
| DESIGNER OF RECORD. |
| NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE |
| THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W. |
| P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE |
| MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE |
| SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO |
| THE BUILDING OFFICIAL ROBERT BROWN. |
| |
| SHEET: FINISHES. UNIT: |
| FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR |
| INSULATION (FBC-B 2010) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE |
| ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| |
| WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| THE PERMIT PACKAGE. |
| |
| A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| |