Plan Review Notes
Plan Review Notes For Permit 18031052
Permit Number 18031052
Review Stop B
Sequence Number 1
Notes
Date Text
2018-04-06 15:21:08****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. FAIR HOUSING DESIGN MANUAL
  
 A) KITCHEN ISLAND DOES NOT HAVE 40 INCH CLEARANCE ON
 TWO SIDES.
  
 B. PROVIDE 32 INCHES CLEAR AT BATHROOM DOORS.
  
 C. IN THE FAIR HOUSING DESIGN MANUAL CHAPTER 7 SELECT
 WHETHER YOU WILL BE USING A OR B SPECIFICATIONS WHEN
 DESIGNING THE BATHROOMS. SHOW THIS ON THE PLANS AND
 ADJUST LAYOUT ACCORDINGLY.
  
 2. DOORS
  
 A. DOOR 111 NOT SHOWN ON SCHEDULE.
  
 B. PROVIDE INFORMATION ON DOOR 101C. ROLL DOWN SMOKE
 DOOR IF USED. NOTE, SINCE THE ELEVATOR IS PRESSURIZED
 THIS DOOR IS NOT REQUIRED.
  
 3. PROVIDE UNDERLAYMENT USED FOR WOOD FLOOR IN ROOM
 121A GYM. IF PLYWOOD UNDERLAYMENT IS USED SHOW
 COMPLIANCE WITH FBC 603.1 COMBUSTIBLE MATERIALS.
  
 4. PROVIDE THE FOLLOWING FLOOR UNDERLAYMENT SOUND
 PROOFING INFORMATION.
  
 STRUCTURAL BORNE SOUND TEST HAS BEEN RECEIVED.
  
 SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
  
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
 NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE
 THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W.
 P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE
 SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO
 THE BUILDING OFFICIAL ROBERT BROWN.
  
 SHEET: FINISHES. UNIT:
 FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE
 ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  