Plan Review Notes
Plan Review Notes For Permit 18031044
Permit Number 18031044
Review Stop G
Sequence Number 3
Notes
Date Text
2019-01-25 11:38:44PROVISO COMPLIED WITH 1/25/19
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
2018-07-12 12:33:19GAS PROVISO:
 1. PLEASE CORRECT THE FOLLOWING PRIOR TO ROUGH
 INSPECTION.
 A) THE BTU LOADS AND THE DEVELOPED LENGTHS ON THE GAS
 FLOOR PLAN AND RISER DO NOT MATCH THE BTU LOAD ON THE
 SIZING CHART OR MANUFACTURE SPECS. PER FBC FG SEC 402
 B) THE 1? CSST THAT IS SUPPLING 2 BBQ GRILLS IS UNDER
 SIZED AT 200?DEVELOPED LENGTH. IT SHALL BE 11/4 EHD 37
 PER FBC FG TABLE 402.4(16)
  
  
 GAS NOTE:
 1. THE BBQ GRILL SHALL COMPLY WITH FBC FG
 301.3LISTED AND LABELED.
 APPLIANCES REGULATED BY THIS CODE SHALL BE LISTED AND
 LABELED FOR THE APPLICATION IN WHICH THEY ARE USED
 UNLESS OTHERWISE APPROVED IN ACCORDANCE WITH SECTION
 104 OF THE FLORIDA BUILDING CODE, BUILDING. THE
 APPROVAL OF UNLISTED APPLIANCES IN ACCORDANCE WITH
 SECTION 104 OF THE FLORIDA BUILDING CODE, BUILDING
 SHALL BE BASED ON APPROVED ENGINEERING EVALUATION.
 301.4LABELING.
 LABELING SHALL BE IN ACCORDANCE WITH THE PROCEDURES SET
 FORTH IN SECTIONS 301.4.1 THROUGH 301.4.2.3.
  623.1COOKING APPLIANCES.
 COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS, STOVES,
 BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND
 BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI
 Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTRUCTIONS.
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  