2018-06-12 14:04:292ND REVIEW: FBC 2017 6TH EDITION
  
 GAS COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 1. PROVIDE A GAS RISER SHOWING THE LENGTH OF EACH
 SECTION OF PIPE, THE TYPE OF PIPE , PRESSURE OF THE
 SYSTEM AND THE EXISTING AND NEW BTU LOAD ON THE PIPE
 AND FOR EACH NEW APPLIANCE. PER FBC-2014 FUEL GAS,
 SECS. 402.4.1, 402.4.2.
  
 2. PROVIDE THE MANUFACTURE SPECIFICATION FOR THE NEW
 GAS APPLIANCES AND PRESSURE REGULATORS SHALL BE LISTED
 FOR EXTERIOR USE. TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  