Plan Review Notes For Permit 18031044 |
Permit Number |
18031044 |
|
Review Stop |
THRESHOLD |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-15 09:32:13 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 553.79(5), IT APPEARS THAT APPLICANT IS PROPOSING | | (LIMITED) STRUCTURAL RENOVATION TO A THRESHOLD | | BUILDING. IS THIS CORRECT? IF YES, THE FOLLOWING IS | | REQUIRED: | | | | 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT | | OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO | | [email protected]. | | | | 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL | | PROPOSED INSPECTORS. | | | | 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT | | REQUIRED BY FS553.79(7)(D). | | | | 4. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A). | | | | IF ENGINEER FEELS THAT THIS RENOVATION DOES NOT FALL | | UNDER THE DEFINITION OF "THRESHOLD", PLEASE HAVE HIM | | CONTACT ME. | | | | | | |
|