2018-04-24 20:10:1704/24/2018 2ND PLUMBING REVIEW**DENIED**
  
  
 1) ISOMETRIC FOR MASTER BATHROOM SHOWS 2 WET VENTED
 FIXTURE PAST THE DRY VENTED FIXTURE. FBC-R P3108.2.1
 DOES NOT ALLOW MORE THAN 1 WET VENTED FIXTURE TO
 DISCHARGE BEYOND THE DRY VENT.
  
 2) SHT. P-1.01 NOTES SAYS A STUB OUT FOR POOL SPA
 AUTOFILL. BACKFLOW PROTECTION IS REQUIRED TO PROTECT
 THE HOUSE SYSTEM. FBC-R P2902.3
  
 3) BEFORE ANY WORK CAN START A BACKFLOW MUST BE
 INSTALLED AT THE WATER METER (RPZ) WITH SEPERATE PERMIT
 BY A LICENESED PLUMBING CONTRACTOR
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT