Plan Review Notes
Plan Review Notes For Permit 18031029
Permit Number 18031029
Review Stop G
Sequence Number 2
Notes
Date Text
2018-04-24 20:01:2504/24/2018 2ND GAS REVIEW**DENIED**
  
 1) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. THE
 SPECIFICATION SUPPLIED FOR THE POOL HEATER AND THE
 STOVE TOP DOES NOT CONTAIN ANY APPROVAL VERIFICATION.
 YOU DID NOT SUPPLY ANY INFORMATION ON THE OUTSIDE BBQ
 GRILL. PROVIDE THE FULL INSTALLATION MANUAL FOR THE
 TANKLESS WATER HEATERS.
  
 2) IS THE OUTSIDE BBQ GRILL LOCATED UNDER ANY TYPE OF
 ROOF COVERING? A HOOD VENT MAY BE REQUIRED. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  