Plan Review Notes
Plan Review Notes For Permit 18031029
Permit Number 18031029
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-29 07:27:0503/29/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON P 101 UNDER PLUMBING NOTES ITEM 16 IT REFERS TO
 FBC 2014 AS WE ARE NOW IN THE FBC 2017 WHICH IS CURRENT
 SO PLEASE CORRECT THAT NOTE.
 2. THE ISOMETRIC DIAGRAM IS MISSING THE DRAIN FOR THE
 UNDER COUNTER ICE MAKER WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (11)
 3. THE LOAD ON DWV-SYSTEM PIPING SHALL BE COMPUTED IN
 TERMS OF DRAINAGE FIXTURE UNIT (D.F.U.) VALUES IN
 ACCORDANCE WITH TABLE P3004.1.
 4. PLEASE SIZE THE NUMBER OF FIXTURE UNIT ALLOWED TO BE
 CONNECTED TO THE BUILDING DRAIN PER TABLE FBC R
 3005.4.2
 5. SHOWER PAN SEAT IN MASTER MUST BE RECESSED AS WELL
 AS THE PAN AS IT IS A PART OF THE SHOWER. FBC R P2709.1
 CONSTRUCTION.
 6. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  