2018-03-29 07:27:05 | 03/29/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON P 101 UNDER PLUMBING NOTES ITEM 16 IT REFERS TO |
| FBC 2014 AS WE ARE NOW IN THE FBC 2017 WHICH IS CURRENT |
| SO PLEASE CORRECT THAT NOTE. |
| 2. THE ISOMETRIC DIAGRAM IS MISSING THE DRAIN FOR THE |
| UNDER COUNTER ICE MAKER WPB AMENDMENTS TO THE FBC SEC. |
| 107.3.5.3 (11) |
| 3. THE LOAD ON DWV-SYSTEM PIPING SHALL BE COMPUTED IN |
| TERMS OF DRAINAGE FIXTURE UNIT (D.F.U.) VALUES IN |
| ACCORDANCE WITH TABLE P3004.1. |
| 4. PLEASE SIZE THE NUMBER OF FIXTURE UNIT ALLOWED TO BE |
| CONNECTED TO THE BUILDING DRAIN PER TABLE FBC R |
| 3005.4.2 |
| 5. SHOWER PAN SEAT IN MASTER MUST BE RECESSED AS WELL |
| AS THE PAN AS IT IS A PART OF THE SHOWER. FBC R P2709.1 |
| CONSTRUCTION. |
| 6. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A |
| WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS |
| OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN |
| ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB |
| AND WHIRLPOOL BATHTUB VALVES. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |