Plan Review Notes
Plan Review Notes For Permit 18031029
Permit Number 18031029
Review Stop G
Sequence Number 1
Notes
Date Text
2018-03-29 07:28:2303/29/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC.
 G2408.1.
 2. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION FBC FUEL GAS RES. SEC. G2421.1.
 3. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE
 GENERATOR SHOWN ON GAS ISOMERIC P-1.02 APPLIANCE
 SHUTOFF 2017 FBC FUEL GAS RES. SEC. G2420.5, APPLIANCE
 CONNECTION 2017 FBC FUEL GAS RES. SEC. G 2415.15.
 4. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS RES. SEC. G2413.3
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR, WHERE IS
 COMBUSTION AIR PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. 2017 FBC FUEL GAS RES. SEC.
 G2407.1 AND G2439.4.
 6. PE PIPE IN GROUND IT?S NOT ALLOWED, THE INSTALLATION
 OF PLASTIC PIPE SHALL COMPLY WITH SECTIONS G2415.17.1
 THROUGH G2415.17.3.
 7. SHOW ALL REQUIRED HUT OFF VALVES, REGULATORS AND
 DISTANCES, VALVES TO BE LOCATED IN THE SAME ROOM, A
 LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR FBC FUEL GAS RES. SEC.
 G2420.4.
 8. ON YOUR ENERGY EFFICIENCY FORM R405-2017 IT SHOW THE
 WATER HEATER AS BEING ELECTRICAL AND A PLAN SHOW 2 GAS
 TANKLESS THEY MUST COMPLY WITH THE E.F .067 AS REQUIRED
 BY THE TABLE R402A.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  