Date |
Text |
2018-03-29 07:28:23 | 03/29/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC. |
| G2408.1. |
| 2. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION FBC FUEL GAS RES. SEC. G2421.1. |
| 3. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE |
| GENERATOR SHOWN ON GAS ISOMERIC P-1.02 APPLIANCE |
| SHUTOFF 2017 FBC FUEL GAS RES. SEC. G2420.5, APPLIANCE |
| CONNECTION 2017 FBC FUEL GAS RES. SEC. G 2415.15. |
| 4. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM 2017 FBC FUEL GAS RES. SEC. G2413.3 |
| 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR, WHERE IS |
| COMBUSTION AIR PROVIDED BY THE BUILDING?S MECHANICAL |
| VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| REQUIRED VENTILATION AIR. 2017 FBC FUEL GAS RES. SEC. |
| G2407.1 AND G2439.4. |
| 6. PE PIPE IN GROUND IT?S NOT ALLOWED, THE INSTALLATION |
| OF PLASTIC PIPE SHALL COMPLY WITH SECTIONS G2415.17.1 |
| THROUGH G2415.17.3. |
| 7. SHOW ALL REQUIRED HUT OFF VALVES, REGULATORS AND |
| DISTANCES, VALVES TO BE LOCATED IN THE SAME ROOM, A |
| LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR FBC FUEL GAS RES. SEC. |
| G2420.4. |
| 8. ON YOUR ENERGY EFFICIENCY FORM R405-2017 IT SHOW THE |
| WATER HEATER AS BEING ELECTRICAL AND A PLAN SHOW 2 GAS |
| TANKLESS THEY MUST COMPLY WITH THE E.F .067 AS REQUIRED |
| BY THE TABLE R402A. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |