2018-04-04 13:26:04 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| PRESENT. WPB FBC 105.1, 107.2.1 |
| 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. THE FORMAT IN THE FBC RESIDENTIAL SHOULD BE |
| FOLLOWED. THE LOAD CALCULATION PROVIDED IS NOT PER |
| CODE, SHOWING DEMAND APPLIED WHERE IT SHOULD NOT BE AND |
| ALSO MATH IS NOT CORRECT. BASED ON THE NUMBERS PROVIDED |
| ON PLAN AND BY MY CALCULATION, IT APPEARS THAT THE 200 |
| AMP SERVICE SPECIFIED WILL NOT BE SUFFICIENT. HOWEVER, |
| THAT CAN ONLY BE DETERMINED BY AN ACCURATE CALCULATION. |
| NEC 220; FBC RE E3602.2 |
| 3. RISER DIAGRAM SHOWS THREE 3/0 CONDUCTORS WITH A # 6 |
| GROUND IN ALL SERVICE CONDUITS. THE # 6 EQUIPMENT |
| GROUNDING CONDUCTOR SHOULD NOT BE INCLUDED IN THE |
| CONDUIT FROM FPL TO THE METER OR IN THE CONDUIT FROM |
| THE METER TO THE TRANSFER SWITCH. PROVIDE CORRECTION. |
| NEC 250.6; FBC RE E3610.4 |
| 4. NOTE 1 IN REFERENCE TO AFCI PROTECTION IS NOT |
| CORRECT PER NEW CODE ADOPTED: ?ALL BRANCH CIRCUITS THAT |
| SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING |
| ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED.? ADDITIONALLY, THE PLAN SHOWS |
| ONLY THE RECEPTACLE OUTLETS IN THE BEDROOM WITH ?AF? |
| PROTECTION. AS STATED ABOVE, ALL OUTLETS, INCLUDING |
| LIGHTING AND RECEPTACLES, SHALL BE AFCI PROTECTED. |
| PROVIDE CORRECTION. NEC 210.12; FBC RE E3902.16 |
| 5. NOTE # 2 STATES THAT RECEPTACLES SHALL BE TAMPER |
| RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| CORRECTION. NEC 406.12; FBC RE E4002.14 |
| 6. NOTE # 3 REFERENCES THE 2011 NEC, WHICH IS NOT THE |
| CURRENT CODE. IT ALSO REFERENCES FBC SECTION 905.2, |
| WHICH HAS NOTHING TO DO WITH SMOKE ALARMS. PROVIDE |
| CORRECTION. FBC PREFACE, FBC RE R314, 315 |
| 7. NOTE 4 REFERENCES THE 2011 NEC, WHICH IS NOT THE |
| CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE |
| 8. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A |
| SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL |
| GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN |
| ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE |
| EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. |
| NEC 250.53(A)(2); FBC RE E3608.4 |
| 9. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI PROTECTED. |
| PROVIDE CORRECTION. NEC 680.21(C); FBC RE E4203.1.3 |
| 10. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN |
| GARAGE, INCLUDING THE GARAGE DOOR OPENER. PROVIDE |
| CORRECTION. NEC 210.8; FBC RE E3902.2 |
| 11. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 12. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |