2018-04-04 13:26:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE FORMAT IN THE FBC RESIDENTIAL SHOULD BE
 FOLLOWED. THE LOAD CALCULATION PROVIDED IS NOT PER
 CODE, SHOWING DEMAND APPLIED WHERE IT SHOULD NOT BE AND
 ALSO MATH IS NOT CORRECT. BASED ON THE NUMBERS PROVIDED
 ON PLAN AND BY MY CALCULATION, IT APPEARS THAT THE 200
 AMP SERVICE SPECIFIED WILL NOT BE SUFFICIENT. HOWEVER,
 THAT CAN ONLY BE DETERMINED BY AN ACCURATE CALCULATION.
 NEC 220; FBC RE E3602.2
 3. RISER DIAGRAM SHOWS THREE 3/0 CONDUCTORS WITH A # 6
 GROUND IN ALL SERVICE CONDUITS. THE # 6 EQUIPMENT
 GROUNDING CONDUCTOR SHOULD NOT BE INCLUDED IN THE
 CONDUIT FROM FPL TO THE METER OR IN THE CONDUIT FROM
 THE METER TO THE TRANSFER SWITCH. PROVIDE CORRECTION.
 NEC 250.6; FBC RE E3610.4
 4. NOTE 1 IN REFERENCE TO AFCI PROTECTION IS NOT
 CORRECT PER NEW CODE ADOPTED: ?ALL BRANCH CIRCUITS THAT
 SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED.? ADDITIONALLY, THE PLAN SHOWS
 ONLY THE RECEPTACLE OUTLETS IN THE BEDROOM WITH ?AF?
 PROTECTION. AS STATED ABOVE, ALL OUTLETS, INCLUDING
 LIGHTING AND RECEPTACLES, SHALL BE AFCI PROTECTED.
 PROVIDE CORRECTION. NEC 210.12; FBC RE E3902.16
 5. NOTE # 2 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 6. NOTE # 3 REFERENCES THE 2011 NEC, WHICH IS NOT THE
 CURRENT CODE. IT ALSO REFERENCES FBC SECTION 905.2,
 WHICH HAS NOTHING TO DO WITH SMOKE ALARMS. PROVIDE
 CORRECTION. FBC PREFACE, FBC RE R314, 315
 7. NOTE 4 REFERENCES THE 2011 NEC, WHICH IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE
 8. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 9. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 680.21(C); FBC RE E4203.1.3
 10. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN
 GARAGE, INCLUDING THE GARAGE DOOR OPENER. PROVIDE
 CORRECTION. NEC 210.8; FBC RE E3902.2
 11. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 12. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  