Plan Review Notes
Plan Review Notes For Permit 18031026
Permit Number 18031026
Review Stop B
Sequence Number 1
Notes
Date Text
2018-04-02 11:03:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVALS (FL22513-R1 & FL22633-R2) FOR
 THE EXTERIOR DOORS THAT WERE SUBMITTED ARE NOT
 COMPLETE. THE REQUIRED EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS ARE MISSING. FAC 61G20-3.001
  
 2) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. FBC 107.3.4
  
 3) THE REVISED PLAN SHEETS A6.0 THAT WERE SUBMITTED ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OF
 RECORD, ALFONSO HERNANDEZ. FS 481 & FAC 471
  
  