2018-06-06 07:08:34 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 600.6(A)(1) DISCONNECT ALL POWER BEFORE IT ENTERS THE |
| SIGN. DISCOONECT IN SIGHT OF SIGN. |
| |
| 600. 6 DISCONNECTS (A) LOCATION. |
| (1) AT POINT OF ENTRY TO A SIGN ENCLOSURE. THE |
| DISCONNECT |
| SHALL BE LOCATED AT THE POINT THE FEEDER CIRCUIT OR |
| BRANCH CIRCUIT(S) |
| SUPPLYING A SIGN OR OUTLINE LIGHTING SYSTEM ENTERS A |
| SIGN ENCLOSURE |
| OR A POLE IN ACCORDANCE WITH 600.5(C)(3) AND SHALL |
| DISCONNECT |
| ALL WIRING WHERE IT ENTERS THE ENCLOSURE OF THE SIGN OR |
| POLE |
| |
| |
| VALUE FOR THE SIGN TO LOW FOR A SIGN THIS SIZE. CITY |
| WILL ASSIGN A VALUE OF $5000 TO THE SIGN. |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| WORK, |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION |
| REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| NATIONAL CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL- |
| SWIFT, MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE |
| SET BY THE BUILDING OFFICIAL |
| |