2018-04-05 12:58:44 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017). |
| |
| 1- PROVIDE COMPLETE EXTERIOR WALL SECTIONS SHOWING LOAD |
| PATH FROM ROOF TO FOOTING AS REQUIRED BY SEC. R601.2 |
| FBC-RESIDENTIAL. STRUCTURAL DETAILS SUBMITTED ARE |
| INCOMPLETE. SPECIFY HOW ARE THE STUDS FASTENED TO TOP |
| AND BOTTOM OF WALL. SPECIFY HOW ARE COLUMNS BETWEEN |
| WINDOWS FASTENED TO TOP AND BOTTOM OF WALL. PROVIDE |
| DETAIL SECTION SHOWING HOW THE SIMPSON HH6 CONNECTORS |
| ARE INSTALLED BETWEEN ADJACENT WINDOWS AS SHOWN ON |
| FLOOR PLAN. |
| SEC. R601.2 REQUIREMENTS. |
| WALL CONSTRUCTION SHALL BE CAPABLE OF ACCOMMODATING ALL |
| LOADS IMPOSED IN ACCORDANCE WITH SECTION R301 AND OF |
| TRANSMITTING THE RESULTING LOADS TO THE SUPPORTING |
| STRUCTURAL ELEMENTS. |
| |
| 2- FLOOR PLAN SHOWS THE REFRIGERATOR INSIDE THE BEDROOM |
| CLOSET. CONSTRUCTION IS NOT CLEAR. APPLIANCES MAY NOT |
| BE ALLOWED INSIDE THE CLOSET. VERIFY WITH THE |
| ELECTRICAL CODE AND REVISE AS REQUIRED. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| 3- A) THE DESIGN PRESSURES SPECIFIED ON THE FLOOR PLAN, |
| NORTH ELEVATION AND WINDOW SCHEDULE DON'T CORRESPOND TO |
| EXPOSURE "C" AS SPECIFIED ON THE CODE COMPLIANCE TABLE. |
| REVISE AS REQUIRED. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| B) THE CORRECT ASCE 7 THAT IS ADOPTED WITH THE CURRENT |
| CODE FBC-2017 IS THE ASCE 7-10 NOT ASCE 7-16. REVISE |
| INFORMATION IN THE CODE COMPLIANCE TABLE AS REQUIRED. |
| . CHAPTER 553 FLORIDA STATUTE. |
| |
| 4- ENERGY CALCULATIONS FORM R405-2017 SUBMITTED: |
| A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| FORM, INCLUDING CORRECT OWNER'S NAME, THE BUILDER'S |
| NAME, PERMIT OFFICE AND JURISDICTION NUMBER. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| B) ITEM #1 IS INCORRECT. CALCULATIONS ARE DONE FOR THE |
| ENTIRE HOUSE. THIS IS NOT NEW CONSTRUCTION. THIS IS AN |
| EXISTING HOUSE. REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| FBC- ENERGY CONSERVATION. |
| |
| C) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| EXISTING AND NEW WINDOWS SHOWING THE U-FACTOR AND SHGC |
| FACTOR SPECIFIED ON THE ENERGY CALCULATIONS AS REQUIRED |
| BY SEC. R405.4.3 FBC- ENERGY CONSERVATION. |
| |
| D) PROVIDE DETAIL AND SPECIFICATIONS SHOWING HOW THE |
| EXISTING CONCRETE BLOCK WALLS COMPLIES WITH THE R-4 |
| INSULATION AS SPECIFIED ON ITEM #9. SEC. R405.4.3 FBC- |
| ENERGY CONSERVATION. NOTE: THIS HOUSE WAS BUILT IN |
| 1929. |
| |
| E) PROVIDE DETAIL AND SPECIFICATIONS SHOWING HOW THE |
| EXISTING FLAT ROOF COMPLIES WITH THE R-30 INSULATION AS |
| SPECIFIED ON ITEM #10. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. NOTE: THIS HOUSE WAS BUILT IN 1929. |
| |
| F) ITEM #15 SHOWS THAT ENERGY CALCULATIONS ARE TAKING |
| THE WHOLE HOUSE FAN (WHF) CREDIT. PERSON PREPARING THE |
| CALCULATIONS TO PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING HOW THE EXISTING HOUSE COMPLIES |
| WITH THIS CREDIT AS REQUIRED BY SEC. R405.7.5 |
| FBC-ENERGY CONSERVATION. |
| |
| G) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS |
| AND GENERATING THE REPORT AS REQUIRED BY SEC. |
| R405.4.2.1 FBC- ENERGY CONSERVATION. |
| |
| H) ROOF TYPE AND MATERIAL SHOWN ON PAGE 2 OF 4 IS |
| INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| I) THE VENT RATIO SHOWN ON PAGE 2 OF 4 IS 1/300. |
| TYPICALLY THE VENT RATIO IS 1/150. PERSON PREPARING THE |
| ENERGY CALCULATIONS TO PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING COMPLIANCE WITH THE 1/300 VENT |
| RATIO AS REQUIRED BY THE EXCEPTION OF SEC. R806.2 |
| FBC-RESIDENTIAL. |
| |
| J) WINDOWS AREA AND OVERHANG DEPTH AND SEPARATION SHOWN |
| ON PAGE 3 OF 4 DOESN'T MATCH PLANS. REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| |
| 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) LAUNDRY EXTERIOR DOOR AS SHOWN ON PLANS. PROVIDE |
| FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO |
| DRAWINGS SUBMITTED. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA |
| PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| CONNECTOR. |
| |
| 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS. |
| |
| |