2018-04-05 12:58:44RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- PROVIDE COMPLETE EXTERIOR WALL SECTIONS SHOWING LOAD
 PATH FROM ROOF TO FOOTING AS REQUIRED BY SEC. R601.2
 FBC-RESIDENTIAL. STRUCTURAL DETAILS SUBMITTED ARE
 INCOMPLETE. SPECIFY HOW ARE THE STUDS FASTENED TO TOP
 AND BOTTOM OF WALL. SPECIFY HOW ARE COLUMNS BETWEEN
 WINDOWS FASTENED TO TOP AND BOTTOM OF WALL. PROVIDE
 DETAIL SECTION SHOWING HOW THE SIMPSON HH6 CONNECTORS
 ARE INSTALLED BETWEEN ADJACENT WINDOWS AS SHOWN ON
 FLOOR PLAN.
 SEC. R601.2 REQUIREMENTS.
 WALL CONSTRUCTION SHALL BE CAPABLE OF ACCOMMODATING ALL
 LOADS IMPOSED IN ACCORDANCE WITH SECTION R301 AND OF
 TRANSMITTING THE RESULTING LOADS TO THE SUPPORTING
 STRUCTURAL ELEMENTS.
  
 2- FLOOR PLAN SHOWS THE REFRIGERATOR INSIDE THE BEDROOM
 CLOSET. CONSTRUCTION IS NOT CLEAR. APPLIANCES MAY NOT
 BE ALLOWED INSIDE THE CLOSET. VERIFY WITH THE
 ELECTRICAL CODE AND REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 3- A) THE DESIGN PRESSURES SPECIFIED ON THE FLOOR PLAN,
 NORTH ELEVATION AND WINDOW SCHEDULE DON'T CORRESPOND TO
 EXPOSURE "C" AS SPECIFIED ON THE CODE COMPLIANCE TABLE.
 REVISE AS REQUIRED. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) THE CORRECT ASCE 7 THAT IS ADOPTED WITH THE CURRENT
 CODE FBC-2017 IS THE ASCE 7-10 NOT ASCE 7-16. REVISE
 INFORMATION IN THE CODE COMPLIANCE TABLE AS REQUIRED.
 . CHAPTER 553 FLORIDA STATUTE.
  
 4- ENERGY CALCULATIONS FORM R405-2017 SUBMITTED:
 A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM, INCLUDING CORRECT OWNER'S NAME, THE BUILDER'S
 NAME, PERMIT OFFICE AND JURISDICTION NUMBER. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) ITEM #1 IS INCORRECT. CALCULATIONS ARE DONE FOR THE
 ENTIRE HOUSE. THIS IS NOT NEW CONSTRUCTION. THIS IS AN
 EXISTING HOUSE. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC- ENERGY CONSERVATION.
  
 C) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 EXISTING AND NEW WINDOWS SHOWING THE U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS AS REQUIRED
 BY SEC. R405.4.3 FBC- ENERGY CONSERVATION.
  
 D) PROVIDE DETAIL AND SPECIFICATIONS SHOWING HOW THE
 EXISTING CONCRETE BLOCK WALLS COMPLIES WITH THE R-4
 INSULATION AS SPECIFIED ON ITEM #9. SEC. R405.4.3 FBC-
 ENERGY CONSERVATION. NOTE: THIS HOUSE WAS BUILT IN
 1929.
  
 E) PROVIDE DETAIL AND SPECIFICATIONS SHOWING HOW THE
 EXISTING FLAT ROOF COMPLIES WITH THE R-30 INSULATION AS
 SPECIFIED ON ITEM #10. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION. NOTE: THIS HOUSE WAS BUILT IN 1929.
  
 F) ITEM #15 SHOWS THAT ENERGY CALCULATIONS ARE TAKING
 THE WHOLE HOUSE FAN (WHF) CREDIT. PERSON PREPARING THE
 CALCULATIONS TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE EXISTING HOUSE COMPLIES
 WITH THIS CREDIT AS REQUIRED BY SEC. R405.7.5
 FBC-ENERGY CONSERVATION.
  
 G) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 H) ROOF TYPE AND MATERIAL SHOWN ON PAGE 2 OF 4 IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I) THE VENT RATIO SHOWN ON PAGE 2 OF 4 IS 1/300.
 TYPICALLY THE VENT RATIO IS 1/150. PERSON PREPARING THE
 ENERGY CALCULATIONS TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE 1/300 VENT
 RATIO AS REQUIRED BY THE EXCEPTION OF SEC. R806.2
 FBC-RESIDENTIAL.
  
 J) WINDOWS AREA AND OVERHANG DEPTH AND SEPARATION SHOWN
 ON PAGE 3 OF 4 DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) LAUNDRY EXTERIOR DOOR AS SHOWN ON PLANS. PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS SUBMITTED.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  
  