Plan Review Notes
Plan Review Notes For Permit 18030944
Permit Number 18030944
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-19 16:24:3006/19/2018 2ND REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. SHEET P-1 UNDER NOTES AND GAS PIPE DESIGN
 INFORMATION ITEM 1 NEED THE CHANGE FROM 2014 FBC FG TO
 2017 FBC FG, PER WPB AMEND TO FBC 107.2.1.
  
 2. THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR
 SHALL BE ONSIDE FOR FINAL GAS INSPECTION. THE GENERATOR
 SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE
 GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200.
  
 3. NFPA 37, SECTION 4.1.4, ENGINES LOCATED OUTDOORS.
 ENGINES, AND THEIR WEATHERPROOF HOUSINGS, IF PROVIDED,
 THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5
 FT. FROM OPENINGS IN WALLS AND AT LEAST 5 FT. FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM
 SEPARATION SHALL NOT BE REQUIRED WHERE EITHER OF THE
 FOLLOWING CONDITIONS EXIST;
  
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 5
 FT. FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE
 RATING OF AT LEAST 1 HOUR.
  
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
  
 4. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED,
 INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM
 THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5.
  
 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1.
  
 7. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS SEC. 402.3
  