Date |
Text |
2018-06-19 16:24:30 | 06/19/2018 2ND REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| |
| 1. SHEET P-1 UNDER NOTES AND GAS PIPE DESIGN |
| INFORMATION ITEM 1 NEED THE CHANGE FROM 2014 FBC FG TO |
| 2017 FBC FG, PER WPB AMEND TO FBC 107.2.1. |
| |
| 2. THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR |
| SHALL BE ONSIDE FOR FINAL GAS INSPECTION. THE GENERATOR |
| SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE |
| GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200. |
| |
| 3. NFPA 37, SECTION 4.1.4, ENGINES LOCATED OUTDOORS. |
| ENGINES, AND THEIR WEATHERPROOF HOUSINGS, IF PROVIDED, |
| THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5 |
| FT. FROM OPENINGS IN WALLS AND AT LEAST 5 FT. FROM |
| STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM |
| SEPARATION SHALL NOT BE REQUIRED WHERE EITHER OF THE |
| FOLLOWING CONDITIONS EXIST; |
| |
| (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 5 |
| FT. FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE |
| RATING OF AT LEAST 1 HOUR. |
| |
| (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| NONCOMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED |
| THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE |
| COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. |
| |
| 4. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| |
| 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC. |
| 409.4. |
| |
| 6. SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1. |
| |
| 7. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM 2017 FBC FUEL GAS SEC. 402.3 |
| |
| LUIS A. CRESPO |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6720 |
| |
| |