Plan Review Notes For Permit 18030848 |
Permit Number |
18030848 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-23 09:57:59 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. THE REVIEW STAMP DOES NOT HAVE A COMPANY NAME ON IT. | | IT IS NOT CLEAR WHO IS APPROVING THIS SUBMITTAL. | | | | 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | ORIGINALS, FS471. THE PLANS WERE PRINTED REDUCED FROM A | | DIGITAL PLAN. A DIGITAL SIGNATURE IS APPLICABLE FOR | | DIGITAL SUBMITTALS; THIS IS A PAPER SUBMITTAL. | | | | 3. THE PLANS ARE REDUCED AND THEREFORE DIFFICULT TO | | READ. FBC 107, PROVIDE FULL SIZE DRAWINGS. | | | | 4. THE CALCULATIONS ARE NOT IN A FORMAT ACCEPTABLE TO | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS. SEE | | FAC61G15-23 FOR GUIDELINES FOR INDEX SHEETS. THE | | CALCULATIONS ARE NOT SIGNED AND SEALED, LACK AN INDEX | | PAGE, LACK A TITLE BLOCK, LACK A SIGNATURE AND SEAL. IF | | AN INDEX SHEET IS NOT UTILIZED, EVERY PAGE SHOULD BE | | SIGNED AND SEALED AND INCLUDE A TITLE BLOCK. | | | | 5. THREE SETS REQUIRED (THRESHOLD JOB), TWO SUBMITTED. |
|