Plan Review Notes
Plan Review Notes For Permit 18030753
Permit Number 18030753
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-22 13:02:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PLAN IS NOT LEGIBLE, FBC 107. PLAN IS TO BE CLEAR AS
 TO SCOPE AND NATURE OF PROPOSED WORK. A COMPLETE PLAN
 REVIEW CANNOT BE DONE AT THIS TIME.
  
 2. STOP WORK ORDER INCLUDED ELECTRICAL, BUT SCOPE OF
 ELECTRICAL DEMO IS NOT SHOWN. PROVIDE AN ELECTRICAL SUB
 PERMIT, FS 489.
  
 3. FBC 107, WHEN WILL AN INTERIOR RENOVATION PERMIT BE
 APPLIED FOR? IS THE SPACE CURRENTLY OCCUPIED? IT IS NOT
 CLEAR WHAT LIFE SAFETY VIOLATIONS MAY HAVE BEEN CREATED
 BY THE WORK DONE WITHOUT A PERMIT. A DEMO PERMIT WILL
 NOT BE ISSUED WITHOUT ADEQUATE INFORMATION.
  
 4. VALUE IS TOO LOW, FBC 109. PROVIDE A REASONABLE
 VALUE.
  
  
  
  