Plan Review Notes
Plan Review Notes For Permit 18030707
Permit Number 18030707
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-23 08:49:321) YOU HAVE SUBMITTED A PLAN THAT SHOWS LANDSCAPING BUT
 NO INFORMATION ON THE IRRIGATION SYSTEM. SHOW THE
 LOCATION OF THE CONTROLLER AND REQUIRED RAIN SENSOR.
 2) WHERE IS THE REQUIRED BACKFLOW PREVENTION DEVICE ON
 THE IRRIGATION SYSTEM? IS THE IRRIGATION SYSTEM
 CONNECTED TO THE DOMESTIC WATER SYSTEM TO THE HOUSE OR
 IS THE IRRIGATION SYSTEM BEING SUPPLIED BY A DEDICATED
 WATER METER FOR THE IRRIGATION SYSTEM. INDICATE THIS ON
 THE PLANS.A SEPARATE PERMIT IS REQUIRED FOR THE
 INSTALLATION OF THE BACKFLOW DEVICE. THE DEVICE SHALL
 BE LEAD FREE AND SHALL BE INSTALLED BY A LICENSED
 PLUMBING CONTRACTOR.TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE BACKFLOW DEVICE SHALL BE
 SUBMITTED WITH THE PLUMBING PERMIT APPLICATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW