Plan Review Notes For Permit 18030622 |
Permit Number |
18030622 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-22 06:54:34 | SUBMIT SIZING CALCULATIONS BASED ON THE PROCEDURE IN | | PLUMBING DRAINAGE INSTITUTE STANDARD PDI-G101. THERE | | ARE SOME NUMBERS WRITTEN ON THE SIDE OF ONE OF THE | | SHEETS BUT I CANNOT TELL HOW YOU ARRIVED AT THESE | | NUMBERS. SUBMIT SIZING CALCULATIONS ON A SEPARATE SHEET | | THAT ARE CLEARLY SHOW HOW YOU ARRIVED AT THE SIZE OF | | THE GREASE TRAP. EACH COMPARTMENT OF THE 3-COMPARTMENT | | SINK NEEDS TO BE CALCULATED.2017 FBC-PLUMBING | | SEC.1003.2, 1003.3.4. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|