Plan Review Notes For Permit 18030590 |
Permit Number |
18030590 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-26 12:00:53 | PERMIT # 18030590 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | 1) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND | | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF | | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE | | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE | | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL | | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO | | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE | | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. | | | | 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | 4) REVIEW AND RESPOND TO BUILDING DEPT. REVIEW | | COMMENTS. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|