Plan Review Notes For Permit 18030566 |
Permit Number |
18030566 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-03-28 16:45:46 | COMMERCIAL ROOFING, THIRD BUILDING REVIEW CHECKLIST. | | CODE: FBC 6TH EDITION (2017). | | | | 1- NOA 15-0731.12 SUBMITTED NOW IS THE SAME NOA THAT | | WAS SUBMITTED THE FIRST TIME. THE SAME COMMENTS FORM | | THE FIRST REVIEW APPLY AGAIN: "PERMIT APPLICATION IS | | FOR ROOF RECOVER. NOA 15-0731.12 SUBMITTED IS NOT FOR | | RECOVER APPLICATIONS. PROVIDE PRODUCT APPROVAL (2 | | COPIES) FOR RECOVER APPLICATIONS AND CLEARLY IDENTIFY | | SELECTED ASSEMBLY. FAC 61G1520-3.001.". | | | | 2- REVISE RAS 117 CALCULATIONS SUBMITTED. NEED TO BE | | REVISED REFERENCING THE NEW CURRENT PRODUCT APPROVAL AS | | REQUIRED BY ITEM #1 ABOVE. SEC. 1609 FBC-BUILDING. | | ALSO, ENGINEER TO CHECK THE DESIGN PRESSURES OF | | SELECTED ASSEMBLY AND CONSTRUCTION TYPE TO MATCH | | SELECTED ASSEMBLY. COORDINATE WITH ITEM #1 ABOVE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|