2018-03-14 08:54:53COMMERCIAL ROOFING, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- PERMIT APPLICATION IS FOR ROOF RECOVER. NOA
 15-0731.12 SUBMITTED IS NOT FOR RECOVER APPLICATIONS.
 PROVIDE PRODUCT APPROVAL (2 COPIES) FOR RECOVER
 APPLICATIONS AND CLEARLY IDENTIFY SELECTED ASSEMBLY.
 FAC 61G1520-3.001.
  
 2- NOA SUBMITTED IS MISSING THE LAST PAGE THAT LIST ALL
 GENERAL AND SYSTEM LIMITATIONS. PROVIDE COMPLETE NOA.
 FAC 61G1520-3.001.
  
 3- SUBMIT ALL THE INFORMATION REQUIRED BY ALL THE
 GENERAL AND SYSTEMS LIMITATIONS REQUIRED IN THE PRODUCT
 APPROVAL SUBMITTED FOR RECOVER APPLICATIONS. FOR
 EXAMPLE, PULL OUT TESTING (TAS 105), MOISTURE SURVEYS
 (TAS 126), ETC. REVIEW ALL THE SYSTEMS LIMITATIONS AND
 PROVIDE ALL L REQUIRED TESTING (2 COPIES). SEC.
 107.2.1.2 CITY AMENDMENTS.
  
 4- PROVIDE RAS 117 CALCULATIONS (2 COPIES) IF SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES AND IF
 SELECTED ASSEMBLY ALLOWS FASTENER ENHANCEMENT. SEC.
 1609 FBC-BUILDING.
  
  