Plan Review Notes For Permit 18030562 |
Permit Number |
18030562 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-24 13:09:23 | 2ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION | | CODE, WEST PALM BEACH AMENDMENTS TO THE FBC-17 | | PERMIT #18030562 | | 3/15/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) COMMENT #1 FROM THE 1ST REVIEW NOT COMPLETELY | | ADDRESSED. THE HVAC PLANS SHALL BE PREPARED BY A FL. | | LICENSED ENGINEER, OR BY THE INSTALLING CONTRACTOR- | | GARRETT AC- IN COMPLIANCE WITH SECTION 105.3.1.2 (3) | | WPB AMENDMENTS TO THE FBC-17. PLEASE REMOVE NAME OF | | | | 2) 2ND REQUEST FOR THE OWNER OR OWNER'S AGENT TO | | PROVIDE CERTIFICATION SIGNATURE AND DATE ON PAGE 1 OF | | ENERGYGAUGE FORM R405-2017. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|