2018-03-15 07:16:34 | 03/15/2018 **1ST GAS REVIEW DENIED ** |
| |
| 1. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN AT THE METER PER 2017 FBC FUEL GAS RES. |
| SEC. G2413.2. |
| 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| DRYERS AND COOK-TOP). WHERE COMBUSTION AIR IS PROVIDED |
| BY THE BUILDING?S MECHANICAL VENTILATION SYSTEM, THE |
| SYSTEM SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE |
| IN ADDITION TO THE REQUIRED VENTILATION AIR. THE |
| MANUFACTURER'S SPECIFICATIONS SHALL NOTE THE CFM'S THAT |
| ARE BEING EXHAUSTED BY THE DRYER. |
| 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| DETAILS OF THE GAS VENT(S) FOR DRYER PER 2017 FBC FUEL |
| GAS RES. SECS. G2426 THUR G2429.1. |
| 4. SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC. |
| G2408.1. (POOL HEATER, COOK-TOP, DRYER, GENERATOR AND |
| FIRE PIT) GAS APPLIANCES SHALL BE LISTED AND LABELED. |
| THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES/EQUIPMENT SHALL BE ONSIDE AT THE TIME OF |
| INSPECTION. 2017 FBC FUEL GAS RES. SEC. G2413.2 AND |
| G2404.3. |
| 5. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM 2017 FBC FUEL GAS RES. SEC. G2413.3. |
| 6. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION 2017 FBC FUEL GAS RES. SEC. G2421.1. |
| 7. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THROUGH |
| THE EXTERIOR WILL BE PROTECTED. WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1. |
| 8. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 9. SHOW SEDIMENT TRAPS ON ISOMETRIC DOWNSTREAM OF THE |
| APPLIANCE SHUTOFF VALVE AS CLOSE TO THE INLET OF THE |
| APPLIANCE AS PRACTICAL 2017 FBC FUEL GAS RES. SEC. |
| G2419.4 (408.4) SEDIMENT TRAP. |
| 10. THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR |
| SHALL BE ONSIDE FOR FINAL GAS INSPECTION. THE GENERATOR |
| SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE |
| GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200. |
| 11. NFPA 37, SECTION 4.1.4, ENGINES LOCATED OUTDOORS. |
| ENGINES, AND THEIR WEATHERPROOF HOUSINGS, IF PROVIDED, |
| THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5 |
| FT. FROM OPENINGS IN WALLS AND AT LEAST 5 FT. FROM |
| STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM |
| SEPARATION SHALL NOT BE REQUIRED WHERE EITHER OF THE |
| FOLLOWING CONDITIONS EXIST; |
| |
| (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 5 |
| FT. FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE |
| RATING OF AT LEAST 1 HOUR. |
| (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| NONCOMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED |
| THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE |
| COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |