Plan Review Notes
Plan Review Notes For Permit 18030429
Permit Number 18030429
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-20 06:17:141) THE 3 COMPARTMENT SINK SHALL BE INDIRECTLY WASTED TO
 THE GREASY WASTE LINE PER THE 2017 FBC-PLUMBING
 SEC.801.1.8.
 2) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE
 GREASE INTERCEPTOR. IF IT IS LOCATED IN A PARKING AREA
 IT SHALL BE EQUIPPED WITH A TRAFFIC LID.
 3) THE DISCHARGE LINE FROM THE INTERCEPTOR SHALL BE A
 MINIMUM OF 4 INCH TO ACCOMMODATE THE INSTALLATION OF A
 4 INCH TWO WAY CLEANOUT THAT IS TO BE USED AS A
 SAMPLING PORT FOR THE CITY OF WPB UTILITIES DEPT.
 4) A TWO WAY CLEANOUT IS REQD. ON THE INLET TO THE
 GREASE INTERCEPTOR PER THE CITY OF WPB UTILITIES.
 5) SUBMIT DOCUMENTATION FROM ENDURA THAT THIS UNIT IS
 APPROVED FOR EXTERIOR INSTALLATION. THE INSTALLATION
 MANUAL ON THE WEBSITE ONLY SHOWS AN INTERIOR
 INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  