Plan Review Notes For Permit 18030429 |
Permit Number |
18030429 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-20 06:17:14 | 1) THE 3 COMPARTMENT SINK SHALL BE INDIRECTLY WASTED TO | | THE GREASY WASTE LINE PER THE 2017 FBC-PLUMBING | | SEC.801.1.8. | | 2) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE | | GREASE INTERCEPTOR. IF IT IS LOCATED IN A PARKING AREA | | IT SHALL BE EQUIPPED WITH A TRAFFIC LID. | | 3) THE DISCHARGE LINE FROM THE INTERCEPTOR SHALL BE A | | MINIMUM OF 4 INCH TO ACCOMMODATE THE INSTALLATION OF A | | 4 INCH TWO WAY CLEANOUT THAT IS TO BE USED AS A | | SAMPLING PORT FOR THE CITY OF WPB UTILITIES DEPT. | | 4) A TWO WAY CLEANOUT IS REQD. ON THE INLET TO THE | | GREASE INTERCEPTOR PER THE CITY OF WPB UTILITIES. | | 5) SUBMIT DOCUMENTATION FROM ENDURA THAT THIS UNIT IS | | APPROVED FOR EXTERIOR INSTALLATION. THE INSTALLATION | | MANUAL ON THE WEBSITE ONLY SHOWS AN INTERIOR | | INSTALLATION. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|