2018-03-14 07:12:45 | 03/14/2018 **1ST GAS REVIEW DENIED ** |
| |
| 1. THE TANK-LESS WATER HEATER TAKAGI HAS NO RECORD IN |
| THE CITY OF A PERMIT OR INSPECTION ON THIS PROPERTY FOR |
| A GAS SYSTEM. THERE WAS A PERMIT IN 2017 BUT IT WAS |
| ONLY AS A PLUMBING WHICH WAS REISSUED FROM 2006 WHEN IT |
| WAS REVOKED. PLEASE REFER TO THE COMMENT BELOW TO |
| EXPEDITE THIS REVIEW FOR COMPLIANCE. |
| 2. SUBMIT PLAN SHOWING A DRAWING OF THE LOCATION OF THE |
| TANK-LESS WATER HEATER AND DISTANCE OF ANY OPERABLE |
| DOORS OR WINDOWS IN RELATION TO THE WATER HEATER, IF |
| THE WATER HEATER IS OUTSIDE OR INDOORS. INDICATE ON THE |
| PLAN IF THE TANK-LESS WATER HEATER IS THE ONLY GAS |
| APPLIANCE IN THIS SYSTEM? IF NOT, SUBMIT A COMPLETE GAS |
| RISER SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE |
| DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, THE BTU |
| LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, THE TYPE |
| OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. THESE |
| REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. THE |
| LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB |
| AMENDMENTS TO THE FBC SEC 107.2.1. |
| 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| FG SEC 402.3. |
| 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC FG SEC 402.2. |
| 6. ELECTRIC POWER AND A SEPARATE BREAKER WILL BE |
| REQUIRED FOR THIS UNIT IF THERE IS NOT ONE IN PLACE AND |
| A SEPARATE PERMIT MAY BE REQUIRED. |
| 7. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC 107.2.1. |
| 8. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FG SEC |
| 401.4, 401.8, 402.1, 402.2, & 402.3. |
| 9. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FG 410.1. |
| 10. SUMMITED TANK-LESS WATER HEATERS MANUFACTURE |
| SPECIFICATION AND MUST BE ON SITE FOR INSPECTION |
| REFERENCE. |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |