Plan Review Notes
Plan Review Notes For Permit 18030398
Permit Number 18030398
Review Stop G
Sequence Number 1
Notes
Date Text
2018-03-14 07:12:4503/14/2018 **1ST GAS REVIEW DENIED **
  
 1. THE TANK-LESS WATER HEATER TAKAGI HAS NO RECORD IN
 THE CITY OF A PERMIT OR INSPECTION ON THIS PROPERTY FOR
 A GAS SYSTEM. THERE WAS A PERMIT IN 2017 BUT IT WAS
 ONLY AS A PLUMBING WHICH WAS REISSUED FROM 2006 WHEN IT
 WAS REVOKED. PLEASE REFER TO THE COMMENT BELOW TO
 EXPEDITE THIS REVIEW FOR COMPLIANCE.
 2. SUBMIT PLAN SHOWING A DRAWING OF THE LOCATION OF THE
 TANK-LESS WATER HEATER AND DISTANCE OF ANY OPERABLE
 DOORS OR WINDOWS IN RELATION TO THE WATER HEATER, IF
 THE WATER HEATER IS OUTSIDE OR INDOORS. INDICATE ON THE
 PLAN IF THE TANK-LESS WATER HEATER IS THE ONLY GAS
 APPLIANCE IN THIS SYSTEM? IF NOT, SUBMIT A COMPLETE GAS
 RISER SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE
 DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, THE BTU
 LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, THE TYPE
 OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. THESE
 REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB
 AMENDMENTS TO THE FBC SEC 107.2.1.
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FG SEC 402.3.
 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FG SEC 402.2.
 6. ELECTRIC POWER AND A SEPARATE BREAKER WILL BE
 REQUIRED FOR THIS UNIT IF THERE IS NOT ONE IN PLACE AND
 A SEPARATE PERMIT MAY BE REQUIRED.
 7. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC 107.2.1.
 8. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FG SEC
 401.4, 401.8, 402.1, 402.2, & 402.3.
 9. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FG 410.1.
 10. SUMMITED TANK-LESS WATER HEATERS MANUFACTURE
 SPECIFICATION AND MUST BE ON SITE FOR INSPECTION
 REFERENCE.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  