Plan Review Notes
Plan Review Notes For Permit 18030334
Permit Number 18030334
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-03-09 11:43:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE DDCA IS NOT LOCATED IN A POSITION THAT MEETS THE
 REQUIREMENTS OF NFPA 24.
  
  
  
 6.2.10* ALL CONTROL VALVES SHALL BE LOCATED WHERE
 ACCESSIBLE AND
 FREE OF OBSTRUCTIONS.
  
 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS
 FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE
 OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FT (12 M)
 FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR
 VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH
 SECTION 6.4
 (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT
 LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 BACKFLOW
 PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL
 BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M)
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5)*A NONINDICATING VALVE, SUCH AS AN UNDERGROUND GATE
 VALVE
 WITH AN APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH,
 LOCATED NOT LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 NONINDICATING
 VALVE, SUCH AS AN UNDERGROUND GATE VALVE WITH AN
 APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH, SHALL
 BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M)
 BUT
 AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF THE
 WALL
 FACING THE BACKFLOW PREVENTER.
 (6) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE
 FROM THE EXTERIOR
 (7) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE
 FROM THE EXTERIOR AS PERMITTED BY THE AUTHORITY HAVING
 JURISDICTION
  
 PLEASE SHOW COMPLIANCE WITH ONE OF THE ABOVE.
  
  
 2) A LICENSED UNDERGROUND CONTRACTOR IS REQUIRED TO
 COMPLETE THIS WORK. ONE IS NOT INDICATED.
  
 PLEASE ENSURE COMPLIANCE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  