2018-03-09 11:43:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THE DDCA IS NOT LOCATED IN A POSITION THAT MEETS THE |
| REQUIREMENTS OF NFPA 24. |
| |
| |
| |
| 6.2.10* ALL CONTROL VALVES SHALL BE LOCATED WHERE |
| ACCESSIBLE AND |
| FREE OF OBSTRUCTIONS. |
| |
| 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS |
| FOR FIRE |
| PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH |
| ONE |
| OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED: |
| (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| FT (12 M) |
| FROM THE BUILDING |
| (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| POST |
| INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE |
| BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| INDICATOR |
| VALVE. |
| (2) A WALL POST INDICATOR VALVE |
| (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| ACCORDANCE WITH |
| SECTION 6.4 |
| (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| VALVE NOT |
| LESS THAN 40 FT (12 M) FROM THE BUILDING |
| (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| BACKFLOW |
| PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL |
| BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M) |
| BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| THE WALL FACING THE BACKFLOW PREVENTER. |
| (5)*A NONINDICATING VALVE, SUCH AS AN UNDERGROUND GATE |
| VALVE |
| WITH AN APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH, |
| LOCATED NOT LESS THAN 40 FT (12 M) FROM THE BUILDING |
| (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| NONINDICATING |
| VALVE, SUCH AS AN UNDERGROUND GATE VALVE WITH AN |
| APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH, SHALL |
| BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M) |
| BUT |
| AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF THE |
| WALL |
| FACING THE BACKFLOW PREVENTER. |
| (6) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| ACCESSIBLE |
| FROM THE EXTERIOR |
| (7) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| ACCESSIBLE |
| FROM THE EXTERIOR AS PERMITTED BY THE AUTHORITY HAVING |
| JURISDICTION |
| |
| PLEASE SHOW COMPLIANCE WITH ONE OF THE ABOVE. |
| |
| |
| 2) A LICENSED UNDERGROUND CONTRACTOR IS REQUIRED TO |
| COMPLETE THIS WORK. ONE IS NOT INDICATED. |
| |
| PLEASE ENSURE COMPLIANCE. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |