Plan Review Notes
Plan Review Notes For Permit 18030309
Permit Number 18030309
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-26 09:03:321ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. G1.03 PLEASE SHOW COMPLIANCE WITH THE
 FOLLOWING: FBC ACC
 A) 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
 B) 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE
 36 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
 C) 609.4 POSITION OF GRAB BARS. 33 INCHES MINIMUM AND
 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO
 THE TOP OF THE GRIPPING SURFACE,
  
 2. SHT. 14.101 DETAIL #01 PROVIDE DIMENSIONS FOR KNEE
 AND TOE CLEARANCE. PER FBC ACC 306
  
 3. PLEASE PROVIDE A CLEAR SCOPE OF PLUMBING WORK THIS
 SET OF PLANS HAD SOME DETAILS BUT DO NOT SHOW AND
 PLUMBING ON THE FLOOR PLAN OF THE WEST TOWER AND THERE
 WAS NO PLUMBING SHOWN ON THE DEMO PLAN FOR THE EAST AND
 WEST TOWERS. PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  