Notes |
Date |
Text |
2018-03-21 17:22:03 | 1ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION | | CODES | | PERMIT #18030309 | | 3/21/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | HP WEST SYSTEM - SECTION C403.2.1 FBC-17 ENERGY | | CONSERVATION. | | | | 2) M1.001: SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY | | AIR SYSTEM OF HP WEST- SECTION 606.2.1. | | | | 3) PLEASE UPDATE ALL CODE REFERENCES TO THE FLORIDA | | BUILDING CODES SIXTH EDITION 2017. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|