Notes
Date Text
2018-03-26 09:56:051ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. G1.03 PLEASE SHOW COMPLIANCE WITH THE
 FOLLOWING: FBC ACC
 A) 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
 B) 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE
 36 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
 C) 609.4 POSITION OF GRAB BARS. 33 INCHES MINIMUM AND
 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO
 THE TOP OF THE GRIPPING SURFACE,
  
 2. SHT. 14.101 DETAIL #01 PROVIDE DIMENSIONS FOR KNEE
 AND TOE CLEARANCE. PER FBC ACC 306
  
 3. PLEASE SHOW THE CLEAR FLOOR SPACE WITH THE
 DIMENSIONS SHOWN, FOR THE TOILETS, LAVATORY'S AND WATER
 FOUNTAIN. PER FBC ACC 604.3.1 - 606.2 - 602.2
  
 4. THE TOILET PAPER DISPENSER SHALL BE MOUNTED ON THE
 SIDE WALL IN FRONT OF THE TOILET SHT. I1.401 + I1.402
 SHOW IT ON THE REAR WALL IT SHALL COMPLY WITH FBC ACC
 604.7
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 602.1 + 602.2 +
 602.4 + 602.7
  
 7. PLEASE SHOW ON THE WATER ISOMETRIC THE AIR HAMMER
 ARRESTORS AND SHUT OFF VALVES COMPILING WITH FBC PL
 604.9 + 606.1 (5)
  
 8. THE ISOMETRIC DRAWINGS ARE TO CONGESTED TO VERIFY
 CODE COMPLIANCE PLEASE EXPAND THE WATER AND SANITARY
 ISOMETRIC . PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  