2018-03-26 09:56:05 | 1ST REVIEW: FBC 2017 6TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. G1.03 PLEASE SHOW COMPLIANCE WITH THE |
| FOLLOWING: FBC ACC |
| A) 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL |
| COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM) |
| MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE |
| WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. |
| B) 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE |
| 36 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE |
| CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM) |
| MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON |
| THE OTHER SIDE. |
| C) 609.4 POSITION OF GRAB BARS. 33 INCHES MINIMUM AND |
| 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO |
| THE TOP OF THE GRIPPING SURFACE, |
| |
| 2. SHT. 14.101 DETAIL #01 PROVIDE DIMENSIONS FOR KNEE |
| AND TOE CLEARANCE. PER FBC ACC 306 |
| |
| 3. PLEASE SHOW THE CLEAR FLOOR SPACE WITH THE |
| DIMENSIONS SHOWN, FOR THE TOILETS, LAVATORY'S AND WATER |
| FOUNTAIN. PER FBC ACC 604.3.1 - 606.2 - 602.2 |
| |
| 4. THE TOILET PAPER DISPENSER SHALL BE MOUNTED ON THE |
| SIDE WALL IN FRONT OF THE TOILET SHT. I1.401 + I1.402 |
| SHOW IT ON THE REAR WALL IT SHALL COMPLY WITH FBC ACC |
| 604.7 |
| |
| 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| |
| 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 602.1 + 602.2 + |
| 602.4 + 602.7 |
| |
| 7. PLEASE SHOW ON THE WATER ISOMETRIC THE AIR HAMMER |
| ARRESTORS AND SHUT OFF VALVES COMPILING WITH FBC PL |
| 604.9 + 606.1 (5) |
| |
| 8. THE ISOMETRIC DRAWINGS ARE TO CONGESTED TO VERIFY |
| CODE COMPLIANCE PLEASE EXPAND THE WATER AND SANITARY |
| ISOMETRIC . PER WPB AMEND TO FBC 107.2.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |