2018-03-23 10:32:46FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT
 IS FOR THE SERVICE TO CONFIRM THE STATED AIC RATING OF
 THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS
 ADEQUATE. NEC 110.9, 110.10
  
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
  
 PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 210.64 ELECTRICAL SERVICE AREAS AT LEAST ONE 125-VOLT,
 SINGLE-PHASE, 15- OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED WIT HIN 15 M (50 FT) OF THE
 ELECTRICAL SERVICE EQUIPMENT.