Plan Review Notes For Permit 18030288 |
Permit Number |
18030288 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-23 10:32:46 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT | | IS FOR THE SERVICE TO CONFIRM THE STATED AIC RATING OF | | THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS | | ADEQUATE. NEC 110.9, 110.10 | | | | PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED | | WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT | | AVAILABLE PER NEC 110.24. | | | | PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | | 210.64 ELECTRICAL SERVICE AREAS AT LEAST ONE 125-VOLT, | | SINGLE-PHASE, 15- OR 20-AMPERE-RATED RECEPTACLE OUTLET | | SHALL BE INSTALLED WIT HIN 15 M (50 FT) OF THE | | ELECTRICAL SERVICE EQUIPMENT. |
|